Case Expansion Monitor Maintenance
10. Press RESET switch on system monitor. Verify
that ALERT and DANGER LEDs remain on and
steady.
11. Reduce the power supply voltage to below the alarm set points and observe that the ALERT
and DANGER LEDs go off (if non-latching alarm jumper is installed). Press RESET switch
on system monitor to reset latching alarms.
18