84417-01
LED DISPLAY
A
B
CONDITION
OK
RELAY DRIVE *
•
OK
•
Channel A and B in operating range
ON
•
OK
0
Respective channel A or B transducer
in Not OK condition or bypassed. *
OFF *
0
OK
•
0
OK
0
Monitor in self test, or both
transducers in Not OK condition or
bypassed. *
OFF *
( 1 )
OK
0
Flashing at 5 Hz = error encountered
during cyclic test. To read error messages
see section 10, pages 11-15.
Flashing at 1 Hz = Transducer has been
Not OK since last Reset
ON
1 5 1 O K
A • — op( —
ODNO DIRECT 0
OALR D I FF 0
0-9YRASS--0
Case Expansion Monitor Operation
Note: Since each channel in the system controls the OK Relay, either channel can cause a Not
OK Relay conditon (de-energized relay).
* Not OK channel can be bypassed to restore relay OK conditions
•
•
•