Chapter 5 – Parameter List
5-2
PARAM
Description
LCD Keypad
Display
Setting Range
Factory
Default
Adj.
During
Run
Page
DRV-24
Output Current
Ia= 0A Ib= 0A
Ic= 0A It = 0A
View Only
6-7
DRV-26
Keypad Reference Mode
KeyRefMode
Minimum
Spd
Last Spd
Preset Spd 1
Stop
Fault
Disable
Disable
Yes
6-7
DRV-27
Current, Phase U
Ia Current, 0.0A
View Only
6-7
DRV-28
Current, Phase V
Ib Current, 0.0A
View Only
6-7
DRV-29
Current, Phase W
Ic Current, 0.0A
View Only
6-7
DRV-30
Current, Ground
Ground Curr, 0.0A
View Only
6-7
DRV-91
(Note 6)
Drive Mode 2 (Run/Stop
Method)
Drive mode 2
Keypad
Fx/Rx-1
Fx//Rx-2
Fx/Rx-1
No
6-7
DRV-92
Frequency Mode 2 (Frequency
Setting Method)
Freq mode 2
Keypad-1
Keypad-2
V1
V1S
I
V1+I
Pulse
Int. 485
Ext. PID
Keypad-1
No
6-7
The gray-highlighted parameters are hidden parameters and will only appear when the related functions are set.
Note 1
: To change display from Hz. To RPM, see DRV 17.
Note 2
: When operating in PI Mode (APP02 set to “yes”), the Set point will be displayed when stopped. The units
of the set point are selected using I/O-86. When running, speed is displayed in Hz.
Note 3
: Only displayed when APP-02 is set to “yes” (PI Mode).
Note 4
: Only displayed when APP-80 is set to “yes” (Ext. Process PI Mode).
Note 5
: DRV21 - 23 are only displayed when I/O 20 - 27 are set to “Speed-L, -M, -H”.
Note 6
: DRV91, 92 are only displayed when I/O 20 - 27 is set to “LOC/REM”.
Содержание RSi SG Series
Страница 10: ......
Страница 35: ...Notes...
Страница 36: ......
Страница 56: ...3 1 Notes...
Страница 65: ...Notes...
Страница 66: ......
Страница 87: ...Notes...
Страница 88: ......
Страница 96: ...6 8 NOTES...
Страница 112: ...6 24 NOTES...
Страница 148: ...6 60 NOTES...
Страница 172: ......
Страница 188: ...Notes...
Страница 198: ...Notes...
Страница 212: ...iv...
Страница 217: ......