Chapter 3 - Installation
3-3
3.2
Wiring
3.2.1
Basic
Wiring
1) For 7.5~40 HP (5.5~30kW)
Control Circuit
Main Power Circuit
AC Input
50/60 Hz
U
V
W
G
R(L1)
S(L2)
T(L3)
N(-)
DB Unit(Optional)
DB Resistor
(Optional)
3
MCCB(Option)
M1
M2
M3
M4
M6
M8
M7
MOTOR
Programmable Digital Input 1(Speed L)
Programmable Digital Input 2(Speed M)
Programmable Digital Input 3(Speed H)
Fault Reset (RST)
Jog Frequency Reference (JOG)
Forward Run command (FX)
Reverse Run command (RX)
Common Terminal
P2(+)
P1(+)
DC Bus Choke (Optional )
Dynamic
Braking Unit
(Optional)
P N B1 B2
DC Bus Choke
DB Resistor
M5
Inverter Disable (BX)
V+
V1
5G
V-
I
Analog Power Source (+12V)
+
-
+
-
Analog Power Source (-12V)
Frequency reference (0~20mA or 4~20mA)
Frequency reference (0~12V,V1S : -12~12V)
Frequency reference common terminal
S1
S0
5G
Output Frequency Meter
Output Voltage Meter
Common for output meter signal
Max. output voltage : 12V
Source Max. : 30mA
Sink Max. : 20mA
5G
B0
A0
Frequency Reference (Pulse : 0 ~ 100kHz)
Common for Frequency Reference (Pulse)
5G
NT
External motor thermal detection
A1
C1
A2
C2
A3
C3
A4
C4
C
-
C+
CM
RS485 Signal
RS485 Common
CM
Note: 1) 5G is Common Ground for Analog Input and Outputs.
2) Use terminal V1 for (0~12V) input or V1S for (-12 ~12V input)
)
Fault Contact Output
250VAC (DC30V), 1A
3A
3C
3B
SA
SB
Safety Function (NC) 600V only
Содержание RSi SG Series
Страница 10: ......
Страница 35: ...Notes...
Страница 36: ......
Страница 56: ...3 1 Notes...
Страница 65: ...Notes...
Страница 66: ......
Страница 87: ...Notes...
Страница 88: ......
Страница 96: ...6 8 NOTES...
Страница 112: ...6 24 NOTES...
Страница 148: ...6 60 NOTES...
Страница 172: ......
Страница 188: ...Notes...
Страница 198: ...Notes...
Страница 212: ...iv...
Страница 217: ......