Chapter 3 - Installation
3-8
Type
Symbol
Name
Description
Input sig
nal
Digital Inputs
Functions (d
efaults)
Additional F
unctions (I/O
-20 ~ I/O-27)
M1, M2, M3
Multi-Function
Input 1, 2, 3
Defines Multi-Function Inputs.
(Factory setting: Multi-Step Frequency 1, 2, 3)
FX [M7]
Forward Run
Command
Forward Run When Closed and Stopped When Open.
RX [M8]
Reverse Run
Command
Reverse Run When Closed and Stopped When Open.
JOG [M6]
Jog Frequency
Reference
Runs at Jog Frequency when the Jog Signal is ON. The Direction
is set by the FX (or RX) Signal. Jog Speed is set with I/O-30.
BX [M5]
Inverter Disable
When the BX Signal is ON the output of the drive is turned off.
When the application uses an Electrical Brake to Stop, BX can
be used to turn off the output signal when the brake is applied.
RST [M4]
Fault Reset
Used for fault reset.
CM
Sequence Common
(NPN) / 24V Com
Common terminal for NPN contact input and also common for
an external 24V supply.
24
Sequence Common
(PNP) / Ext.
+24VDC supply
24 V terminal for PNP contact input.
Can also be used as a 24VDC external power supply (maximum
output: +24V, 50mA).
Analog Frequency Setting
V+, V-
Frequency Setting
Power (+12V,-12V)
Power supply for Analog Frequency Setting.
(maximum output: +12V, 100mA, -12V, 100mA.)
V1
Frequency
Reference
(Voltage)
Used by a DC 0-12V or –12~ 12 V input to set the Frequency
Reference. (Input Resistance 20 K
Ω
).
I
Frequency
Reference (Current)
Used by a 0/4-20mA input to set the frequency reference.
(Input Resistance 249
Ω
).
A0, B0
Frequency setting
(Pulse)
Used by a pulse input to set the frequency reference.
5G (7.5~40HP)
CM (50~700HP)
Frequency Setting
Common Terminal
Common terminal for Analog Frequency Reference signals.
Motor
Thermal
Detection
NT (7.5 ~ 40HP)
ET (50 ~125HP)
External motor
thermal detection
Motor thermal sensor input. Used to prevent motor from
overheating by using a NTC or PTC thermal sensor.
RS-485/
Modbus
terminal
C+, C-
RS-485/Modbus
signal High, Low
RS-485/Modbus signals (See Chapter 9 in this manual for more
details.)
CM
RS-485/Modbus
common
Common Gnd. Terminal for RS-485/Modbus interface.
Output signal
Voltage
S0, S1
(5G)
Progammable
Voltage Output for
external monitoring
Voltage output for one of the following: Output Frequency,
Output Current, Output Voltage, DC Link Voltage, Power
(Watts). Default is set to Output Frequency. (Maximum Output
Voltage and Output Current are 0-12V and 30mA).
Contact
3A, 3C, 3B
Fault Contact
Output
Energizes when a fault is present. (AC250V, 1A; DC30V, 1A)
Normal: 3B-3C Closed (3A-3C Open)
Fault: 3A-3C Closed (3B-3C Open)
A1~4,
C1~4
Multi-Function
Output Relays
User defined: Multi-Function Output terminal settings
(AC250V, 1A; DC30V, 1A)
Содержание RSi SG Series
Страница 10: ......
Страница 35: ...Notes...
Страница 36: ......
Страница 56: ...3 1 Notes...
Страница 65: ...Notes...
Страница 66: ......
Страница 87: ...Notes...
Страница 88: ......
Страница 96: ...6 8 NOTES...
Страница 112: ...6 24 NOTES...
Страница 148: ...6 60 NOTES...
Страница 172: ......
Страница 188: ...Notes...
Страница 198: ...Notes...
Страница 212: ...iv...
Страница 217: ......