Chapter 4 - Operation
4-8
(CM on Units 50 HP and larger)
4.1.8
Quickstart
3:
Two
Wire
Start
and
Control
via
4
‐
20mA
Analog
Input
By closing M7 – CM the drive will start in the forward direction.
By closing M8 – CM the drive will start in the reverse direction.
Description:
The following example shows how to configure the drive to operate from a 4-20mA
analog input and a remote two wire start command
. If a three-wire start/stop circuit is required
refer to I/O 20 – 29. One of the inputs can be configured to 3-wire.
[Wiring]
R
S
T
G
U
V
W
M8(RX)
M7(FX)
M6
M5
M4
M3
M2
M1
CM
I
5G
S1
5G
3A
3C
3B
IM
3P
AC
INPUT
4 – 20mA Input
S/W
S0
I
Step
Parameter Name
Parameter
Number
Description
1
Drive Mode
DRV-03
Set it to Fx/Rx-1.
2
Frequency Mode
DRV-04
Set it to I Analog input.
3
Freq. command
setting
DRV-00
Set the frequency command to desired speed via
the analog input.
Содержание RSi SG Series
Страница 10: ......
Страница 35: ...Notes...
Страница 36: ......
Страница 56: ...3 1 Notes...
Страница 65: ...Notes...
Страница 66: ......
Страница 87: ...Notes...
Страница 88: ......
Страница 96: ...6 8 NOTES...
Страница 112: ...6 24 NOTES...
Страница 148: ...6 60 NOTES...
Страница 172: ......
Страница 188: ...Notes...
Страница 198: ...Notes...
Страница 212: ...iv...
Страница 217: ......