84
6 - PARAMETER DESCRIPTION
Kick Level 1
CFN 11
LCD Display
Range
Off, 100 – 800% of FLA
(Default Off)
Description
The Kick Level 1 parameter sets the current level that precedes any ramp when a start is first commanded.
The kick current is only useful on motor loads that are hard to get rotating but then are much easier to move
once they are rotating. An example of a load that is hard to get rotating is a ball mill. The ball mill requires a
high torque to get it to rotate the first quarter turn (90°). Once the ball mill is past 90°of rotation, the material
inside begins tumbling and it is easier to turn.
The kick level is usually set to a low value and then the kick time is adjusted to get the motor rotating. If the
kick time is set to more than 2.0 seconds without the motor rotating, increase the kick current by 100% and
re-adjust the kick time.
See Also
Start Mode parameter on (CFN01) on page 78.
Kick Time 1 parameter on (CFN12) on page 84.
Theory of Operation section 7.3.2, Programming A Kick Current on page 149.
Kick Time 1
CFN 12
LCD Display
Range
0.1 – 10.0 seconds
(Default 1.0)
Description
The Kick Time 1 parameter sets the length of time that the kick current level (CFN11) is applied to the motor.
The kick time adjustment should begin at 0.5 seconds and be adjusted by 0.1 or 0.2 second intervals until the
motor begins rotating. If the kick time is adjusted above 2.0 seconds without the motor rotating, start over
with a higher kick current setting.
z
NOTE:
The kick time adds to the total start time and must be accounted for when setting the UTS time.
See Also
Up To Speed parameter (QST09) on page 77.
Start Mode parameter (CFN01) on page 78.
Kick Level 1 (CFN11) on page 84.
Theory of Operation section 7.3.2, Programming A Kick Current on page 149.
CFN: Kick Lvl 1
11
Off
CFN: Kick Time 1
12
1.0 sec
Содержание RediStart MX3 Series
Страница 9: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 7...
Страница 35: ...3 Installation 27...
Страница 61: ...4 Keypad Operation 53...
Страница 71: ...5 Parameter Groups 63...
Страница 79: ...6 Parameter Description 71...
Страница 145: ...7 Theory of Operation 137...
Страница 188: ...NOTES 180 7 THEORY OF OPERATION...
Страница 189: ...8 Troubleshooting Maintenance 181...
Страница 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Страница 209: ...Appendices 201...
Страница 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...