Digital Input Configuration
I/O 01 - I/O 08
LCD Display
LCD
Description
Range
Off
Off, Not Assigned, Input has no function.
(Default DI02 -DI08)
Stop
Stop Command for 3-wire control.
(Default DI 1)
Fault High
Fault High, Fault when input is asserted, 120V applied. See (I/O 09)
Fault Low
Fault Low, Fault when input is de-asserted, 0V applied. See (I/O 09)
Fault Reset
Reset when input asserted, 120V applied.
Disconnect
Disconnect switch monitor.
Inline Cnfrm
Inline contactor feedback.
Bypass Cnfrm
Bypass/2M, bypass contactor feedback, 2M contactor feedback in
full voltage or Wye-delta.
E OL Reset
Emergency Motor Overload content reset. After an OL trip has
occurred. Reset when input asserted, 120V applied.
Local/Remote
Local/Remote control source, Selects whether the Local Source
parameter or the Remote Source parameter is the control source.
Local Source is selected when input is de-asserted, 0V applied.
Remote Source selected when input asserted, 120V applied.
Heat Disable
Heater disabled when input asserted, 120V applied.
Heat Enable
Heater enabled when input asserted, 120V applied.
Ramp Select
Ramp 2 is enabled when input asserted, 120V applied.
Slow Spd Fwd
Operate starter in slow speed forward mode.
Slow Spd Rev
Operate starter in slow speed reverse mode.
Brake Disabl
Disable DC injection braking.
Brake Enabl
Enable DC injection braking.
Speed Sw NO
Speed Switch Normally Open, 0V applied. See (PFN26) on page 104.
Speed Sw NC
Speed Switch Normally Closed, 120V applied. See (PFN26) on page 104.
Description
I/O parameters 1 - 3 configure which features are performed by the DI 1 to DI 3 terminals.
I/O parameters 4 - 8 configure which features are performed by the DI 4 to DI 8 terminals.
See Also
Local Source parameter (QST04) on page 74.
Remote Source parameter (QST05) on page 74.
Digital Fault Input Trip Time (I/O09) on page 112.
Bypass Feedback Time parameter (I/O25) on page 118.
Heater Level parameter (FUN08) on page 128.
Theory of Operation section 7.1.12, Emergency Motor Overload Reset on page 146.
Theory of Operation section 7.3.7, Dual Acceleration Ramp Control on page 154.
Theory of Operation section 7.8, Wye-Delta Operation on page 168.
Theory of Operation section 7.13, Start/Stop Control with a Hand/Off/Auto Selector Switch on page 176.
111
6 - PARAMETER DESCRIPTION
I/O: DI 8 Config
08
Off
I/O: DI 4 Config
04
Off
I/O: DI 5 Config
05
Off
I/O: DI 6 Config
06
Off
I/O: DI 1 Config
01 Stop
I/O: DI 2 Config
02
Off
I/O: DI 3 Config
03
Off
I/O: DI 7 Config
07
Off
Содержание RediStart MX3 Series
Страница 9: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 7...
Страница 35: ...3 Installation 27...
Страница 61: ...4 Keypad Operation 53...
Страница 71: ...5 Parameter Groups 63...
Страница 79: ...6 Parameter Description 71...
Страница 145: ...7 Theory of Operation 137...
Страница 188: ...NOTES 180 7 THEORY OF OPERATION...
Страница 189: ...8 Troubleshooting Maintenance 181...
Страница 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Страница 209: ...Appendices 201...
Страница 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...