Frequency Trip Time
PFN 16
LCD Display
Range
0.1 – 90.0 seconds
(Default 0.1)
Description
The Frequency Trip Time parameter sets the time that the line frequency must go above the Over Frequency
Trip Level (PFN14) or below the Under Frequency Trip Level (PFN15) parameter before a high or low
frequency fault will occur.
See Also
Over Frequency Level (PFN14) on page 100.
Under Frequency Level (PFN15) on page 100.
PF Lead Trip Level
PFN 17
LCD Display
Range
Off, - 0.80 lag to +0.01 lead
(Default Off)
Description
The amount of power factor lead, before the specified PF Trip Time (PFN19) Fault 35 will occur.
See Also
Power Factor Lag Trip Level (PFN18) on page 101.
Power Factor Trip Time (PFN19) on page 101.
PF Lag Trip Level
PFN 18
LCD Display
Range
Off, - 0.01 lag to +0.80 lead
(Default Off)
Description
The amount of power factor lag, before the specified PF Trip Time (PFN19) Fault 36 will occur.
See Also
Power Factor Lead Trip Level (PFN17) on page 101.
Power Factor Trip Time (PFN19) on page 101.
PF Trip Time
PFN 19
LCD Display
Range
0.1 – 90.0 seconds
(Default 10.0)
Description
The amount of time that the power factor lead level (PFN17) or lag level (PFN18) conditions must exist
beyond the window (PFN19) before a trip will occur.
101
6 - PARAMETER DESCRIPTION
PFN: Frq Trip Tim
16
0.1 sec
PFN: PF Lead Lvl
17
Off
PFN: PF Lag Lvl
18 Off
PFN: PF Trip Time
19
10.0 sec
Содержание RediStart MX3 Series
Страница 9: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 7...
Страница 35: ...3 Installation 27...
Страница 61: ...4 Keypad Operation 53...
Страница 71: ...5 Parameter Groups 63...
Страница 79: ...6 Parameter Description 71...
Страница 145: ...7 Theory of Operation 137...
Страница 188: ...NOTES 180 7 THEORY OF OPERATION...
Страница 189: ...8 Troubleshooting Maintenance 181...
Страница 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Страница 209: ...Appendices 201...
Страница 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...