Kick Level 2
CFN 13
LCD Display
Range
Off, 100 – 800% of FLA
(Default Off)
Description
The Kick Level 2 parameter sets the current level that precedes any ramp when a start is first commanded
when the second ramp is active. Refer to the Kick Level 1 parameter on page 84 for description of operation.
Kick Time 2
CFN 14
LCD Display
Range
0.1 – 10.0 seconds
(Default 1.0)
Description
The Kick Time 2 parameter sets the length of time that the kick current level (CFN11) is applied to the motor
when the second ramp is active. Refer to the Kick Time 1 parameter on page 84 for description of operation.
See Also
Kick Level 1 parameter (CFN11) on page 84.
Digital Input Configuration (I/O 01 - 08) parameters on page 111.
Theory of Operation section 7.3.2, Programming A Kick Current on page 149.
Theory of Operation section 7.3.7, Dual Acceleration Ramp Control on page 154.
Stop Mode
CFN 15
LCD Display
Range
LCD
Description
Coast
(Default)
Coast to Stop
Volt Decel
Open Loop Voltage Deceleration
TT Decel
TruTorque Deceleration
DC Brake
D.C. Braking
85
6 - PARAMETER DESCRIPTION
CFN: Kick Lvl 2
13
Off
CFN: Kick Time 2
14
1.0 sec
CFN: Stop Mode
15 Coast
Содержание RediStart MX3 Series
Страница 9: ...1 Introduction 1...
Страница 15: ...2 Technical Specifications 7...
Страница 35: ...3 Installation 27...
Страница 61: ...4 Keypad Operation 53...
Страница 71: ...5 Parameter Groups 63...
Страница 79: ...6 Parameter Description 71...
Страница 145: ...7 Theory of Operation 137...
Страница 188: ...NOTES 180 7 THEORY OF OPERATION...
Страница 189: ...8 Troubleshooting Maintenance 181...
Страница 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Страница 209: ...Appendices 201...
Страница 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...