7.3.9
Changing Ramp Profiles
The selected ramp profile may be changed during starting by changing the Ramp Select input. When the
Ramp Select input changes during ramping, control switches to the other profile as if it were already in
progress. It does not switch to the beginning of the other profile. Refer to the following example below:
z
NOTE:
Once the motor has achieved an up-to-speed status (UTS), changes to the Ramp Select input have
no effect on the motor operation.
156
7 - THEORY OF OPERATION
Ramp Profile 1
Ramp Profile 2
Initial Current 2
Kick Level 1
Maximum Current
2
Initial Current 1
Maximum Current 1
Kick Time 1
Ramp Time 2
Ramp Time 1
Ramp Select Changed During Start
Ramp 1 Selected
Ramp 2 Selected
Kick Level 2
Kick Time 2
Ramp Time 2
Figure 44: Changing Ramps During Acceleration Example