3.13.4
RS-485 Communication
The RS-485 communications wiring should use shielded twisted pair cable. The shield should only be terminated at one end. The
connections are as follows:
MX RJ45
Module
Description
pin 5
A(-)
RS-485 negative communications connection.
pin 4
B(+)
RS-485 positive communications connection.
pin 8
Com
RS-485 common connection.
3.13.5
RTD Connections
Each Remote RTD Module has connections for up to 8 RTDs. The terminals for the RTD wires are as follows:
•
R- RTD return wire
•
C- RTD compensation wire
•
H- RTD hot wire
Each RTD is connected to the three terminals with the common number. For example, RTD number 5 connects to the terminals
numbered 5R, 5C and 5H.
51
3 - INSTALLATION
REMOTE RTD MODULE
³
Figure 30: Remote RTD Module Wiring