Bennett CNG Spec. 100 Series Operators Manual 

Programming

 

38 

MENU CODE 85 - PRESSURE  SET POINT 

Menu Code 85 is used to input the pressure limit for the product lines. Exceeding pressure limit for 30 seconds will force the dispenser 
into a paused state. The default pressure limit is P30 = 3600 psi or P36 = 4400 psi 

TO ENTER THE PRESSURE SET POINT IN MENU CODE 85, FOLLOW THIS PROCEDURE: 

1.

 

Press the number 

8

 and 

5

, then the [

MODE

]

 

button on the keypad. The PPM display 

shows  the  dispenser  is  in  Menu  Code  85  as  shown  in 

Figure  4.64

.  The  default 

pressure limit for P30 or P36 will be displayed. 

2.

 

To change the setting, use the numeric keypad to enter a new option. 

Note:

 If an 

error is made, press the correct number. The new number will replace the error. 

3.

 

When the desired value appears in  the main display, press the [

ENTER

] button to 

save the selection. 

4.

 

Press the [

CANCEL

] button to exit this Menu Code. 

 

MENU CODE 99  –HOW TO CONFIGURE THE  DISPENSER FOR UNIT  OF MEASURE 

IMPORTANT: 

 

In order to program menu code 99 the electronic calibration switch must be flipped to E-Cal mode. 

Menu Code 99 is used to set the unit of measurement used in the country where the dispenser is located. The second option allows the 
technician to configure the decimal place location. The third option allows the technician to configure temperature units. The fourth 
option is for viewing the electronic calibration settings. This menu code also uses a counter to track the number of times the unit of 
measure, decimal placement, and temperature unit has been changed. Refer to options 1 through 4 for detailed descriptions and 
programming instructions.  

Note: 

Press [

ENTER

] to cycle through the different available options. Use the numeric keypad to select an option. 

 

OPTION 1

 – Program the Unit of Measurement 

 

OPTION 2

 – Decimal Place Configuration  

 

OPTION 3

 – Program Temperature Units 

 

OPTION 4

 – View Electronic Calibration 

OPTION 1  – PROGRAM THE UNIT OF MEASURE  

The

 Unit of Measure

 identifies the unit of measure used in the country where the dispenser is located. There are six available options. 

UNIT OF MEASURE OPTIONS 

 

1

 – (Default) GGE = Gasoline Gallon Equivalent 

 

2

 – GLE = Gasoline Liter Equivalent  

 

– DGE = Diesel Gallon Equivalent 

 

– DLE = Diesel Liter Equivalent 

 

– KG = Kilograms 

 

– LB = Pounds 

To select the unit of measure in Menu Code 99, follow this procedure:

 

 

1.

 

Break the seal on the E-CAL switch and flip the switch to the calibration position. 

2.

 

After the Manager’s Mode has been accessed, press the number 

9

 and 

9

, then the [

MODE

button on the keypad. The PPM display shows the dispenser is in Menu Code 99.  

 

If the dispenser has not been programmed since it came from the factory, disabled will appear in the main display. This is the 
default setting.  

 

The 

0

 (if new) or any other number that appears in the second row under the 1 is a counter. It tracks the number of times this 

setting has been changed. 

3.

 

To change the setting, use the 

1

 through 

6

 buttons on the keypad to enter a new option. The display will show dashes during a new 

selection as shown in 

Figure 4.65

Note

: If an error is made, press the correct number. The new number replaces the error. 

4.

 

Press [

ENTER

] to save your setting and to cycle to the next option. The dashes will disappear after a selection is made and the display 

moves to the Decimal Place Configuration. 

5.

 

Press [

CANCEL

] to exit this menu code. 

 

FIGURE 4.64 – PRESSURE LIMIT 

Sale $ 

Press 

GGE 

4400 

 

 

 

 

 

 

code 

 

-85 

 

 

 

 

 

 

 

 

Sale $ 

GGE 

GGE 

 

 

 

 

 

 

code 

 

-99 

 

 

 

 

 

 

 

 

FIGURE 4.65 – UNIT OF MEASURE 

Содержание CNG Spec. 100 Series

Страница 1: ...S MANUAL This manual has important information for safe installation and operation of this equipment Read and understand this manual before applying power Keep this manual and tell all service personn...

Страница 2: ...6050 Facsimile USA 231 799 6202 Email sales bennettpump com or salesintl bennettpump com Website www bennettpump com For new manuals visit our web page at www bennettpump com IMPORTANT Examine the shi...

Страница 3: ...Bennett CNG Spec 100 Series Operators Manual Bennett Limited Warranty i...

Страница 4: ...Bennett CNG Spec 100 Series Operators Manual ii Page Intentionally Left Blank...

Страница 5: ...ttings or Speed Program the Dispenser 17 Menu Code 7 How to Enter the Type of Dispenser 18 Menu Code 8 How to Change the Decimal Point Locations 21 Menu Code 9 How to Set a No Flow Idle Authorization...

Страница 6: ...ic s Code 1 Display Segment Test 43 Diagnostic s Code 2 Error History 43 Diagnostic s Code 3 CPU Test 44 Diagnostic s Code 4 RAM Test 44 Diagnostic s Code 5 Pump Handle Test 45 Diagnostic s Code 6 Cou...

Страница 7: ...ally every 3 years to ensure safe operation of the vehicle or cylinder manufacture To prevent electric shock keep the electrical parts of the dispenser dry Electronic components are static sensitive U...

Страница 8: ...aintenance of Compressed Natural Gas Vehicle Fueling Facilities UNAUTHORIZED ALTERATION OF BENNETT PRODUCTS DANGER BEFORE PERFORMING ANY TYPE OF SERVICE TO THE DISPENSERS BE SURE TO SHUT OFF ALL ELECT...

Страница 9: ...tablished by the American with Disabilities Act ADA per Chapter 3 Building Blocks Section 308 Reach Ranges and Section 309 Operable Parts The forward and side reach maximum height is 48 inches above t...

Страница 10: ...Bennett CNG Spec 100 Series Operators Manual Safety Information 4 Page Intentionally Left Blank...

Страница 11: ...se width x depth INSIDE 43 3 8 width x 15 1 8 depth OUTSIDE 44 width x 19 depth CNG Series Estimated Shipping Weight pounds GGE 650 lbs 295 kg ENVIRONMENTAL REQUIREMENTS Operating and Storage Temperat...

Страница 12: ...ollowing section provides a description of the controls and instrumentation used on a CNG Spec 100 Dispenser Note Not all dispenser options are shown in Figure 2 1 below FIGURE 2 1 DISPENSER LAYOUT Up...

Страница 13: ...fore and during the fueling process The idle screen shown in Figure 2 2 is an example of how of the module prompts the user with guided instructions Note The display is controlled by the POS Refer to...

Страница 14: ...iagnostics section for complete instructions for using the keypad to read error codes AC OFF MESSAGE The AC OFF message occurs whenever the power has been interrupted or turned off to the dispenser If...

Страница 15: ...vehicle and hang it up in the nozzle boot ending the transaction HOW TO READ THE ELECTRO MECHANICAL TOTALIZER NOTE Because of rounding methods used and the nature of electronic totals versus an analo...

Страница 16: ...Totals with the Magnetic Reed Switch Press the Up Arrow to move through product x totals money mass sale price counters Press ENTER to move from product x to product y TO READ THE MONEY TOTALS ON THE...

Страница 17: ...over 2 Tap the magnet over the mass display print again to read the Mass Totals for Product 1 P12 1 is displayed in the PPM display to indicate the first Mass Total for Product 1 as shown in Figure 3...

Страница 18: ...THIS PROCEDURE 1 Press the 2 button and then the MODE button on the keypad a The main display shows the electro mechanical total as shown in Figure 3 9 b The total number is carried to three decimal p...

Страница 19: ...single sale at one pump 12 Timeout Settings Program to set the timeout for valve switch delay last sale timeout idle timeout 13 Audio Tone Beeper Program to set beeper tone options 14 PPM Price Displa...

Страница 20: ...Instruction Prompt 1 Enabled 63 Handle Masking 0 Disabled 65 Max Fill Pressure P30 3300 P36 4000 Default value based on the grade type selected in mode 7 68 Reported Temperature Units 1 Fahrenheit 80...

Страница 21: ...efore the remaining protected menus can be accessed The display shown in Figure 4 2 appears when the cancel button is pressed HOW TO CHANGE THE 4 DIGIT MANAGER S ACCESS CODE CAUTION To avoid having to...

Страница 22: ...before this mode may be entered NOTE The Price Per Mass reflected in these figures represent a setup with 2 Tier Pricing TO PROGRAM PRICE PER MASS DATA FOLLOW THIS PROCEDURE 1 Press the 4 button and t...

Страница 23: ...chanical totalizers When the first new number is pressed the mass displays zeros and begins rotating the new total into the display 3 Press the ENTER button to save the new value 4 Press the CANCEL bu...

Страница 24: ...icates a gas detector is present with Modbus Slave ID of 2 or 3 0 None Default 1 Add2 2 Add3 3 Both TYPE OF VALVE 1 Solenoid Default 2 Ball TO ENTER DISPENSER CONFIGURATION FOLLOW THIS PROCEDURE To re...

Страница 25: ...or 1 Grade as shown in Figure 4 12 3 If necessary enter the recommended default setting for number of grades using the numeric keypad This option will only accept the options listed above Note If an e...

Страница 26: ...option will only accept the options listed above Note If an error is made press the correct number The new number replaces the error 4 Press ENTER to save setting and to advance to the next option If...

Страница 27: ...the PPM display can be changed Contact an authorized service technician to change from gallons to liters The dispenser is shipped from the factory set for the monetary system in the United States NOT...

Страница 28: ...ade press the 0 button until all three digits are zeros and enter a new number or push the number buttons until the correct number of seconds appears in the mass display NOTE If a 0 is entered in this...

Страница 29: ...10 FOLLOW THIS PROCEDURE 1 After the Menu Code has been accessed press the number 1 and 0 button and then the MODE button on the keypad The main display on an un programmed dispenser will appear as i...

Страница 30: ...s or checking the flow end connections The default timeout is 3 seconds and the maximum timeout is 99 seconds TO PROGRAM THE AMOUNT OF TIME THAT THE VALVE DELAYS IS SHOWN ON THE MAIN DISPLAY FOLLOW TH...

Страница 31: ...he dispenser can be programmed to emit audio tones when certain buttons are pushed or a pump handle is turned on The four options available are 0 No audio tones 1 Audio tone whenever a button on the k...

Страница 32: ...display and cash to the top display requiring FLIP to be turned on Digit Is used to program the dispenser for a four or five digit PPM display 0 Four Digit Display 1 default Five Digit Display Note If...

Страница 33: ...ALS CALCULATION METHOD Menu Code 18 allows the manager to select the method for calculating money totals The first method adds the value on the display to the Money Totals and stores the amount This M...

Страница 34: ...s are on the same communication loop If more than one dispenser is using the same communications loop up to four dispensers To review or change the settings in Manager s Mode 22 press the ENTER button...

Страница 35: ...xit mode 22 PLC LOWEST ADDRESS This option is used to enter the lowest PLC address sent by the PLC if applicable The dispenser needs to know the lowest address sent by the PLC so the dispenser can ver...

Страница 36: ...amount For example if the total money amount for the dispenser is 7 890 123 45 the display appears as in Figure 4 39 b The PPM display window reads P1 1 d for Product 1 Money Total 2 To read the money...

Страница 37: ...ss the button as shown in Figure 4 43 Remember only the number of products selected in Menu Code 7 will be displayed CAUTION THE FOLLOWING PROCEDURE ZEROS ALL THE SHIFT MONEY MASS AND COUNTER TOTALS I...

Страница 38: ...up arrow button or the down arrow button to view the current electronic calibration correction constant for each configured meter product A or product B Once you are viewing the desired meter press E...

Страница 39: ...e MENU CODE 29 HOW TO SET THE RESETTABLE ELECTRONIC MASS TOTALS Menu Code 29 is used to reset the electronic resettable meter totals that accumulate in the dispenser every time a sale is completed Thi...

Страница 40: ...MENU CODE 44 SIMULATOR MODE CAUTION THIS PROCEDURE IS ONLY TO BE USED FOR TROUBLESHOOTING CONTACT BENNETT TECHNICAL SUPPORT PRIOR TO ENTERING THIS MODE IMPORTANT THE CALIBRATION SWITCH MUST BE UNSEAL...

Страница 41: ...s keypad was plugged in for the first time as shown in Figure 4 57 The password in Mode 03 will need to be re entered before proceeding MENU CODE 60 HOW TO SET THE INSTRUCTION PROMPT Menu Code 60 is...

Страница 42: ...d 3 then the MODE button on the keypad The PPM display shows the dispenser is in Menu Code 61 If the dispenser has not been programmed since it came from the factory the number 0 appears in the main d...

Страница 43: ...binet VALVE OPTIONS 0 Off All Valves Off 1 1A Side 1 Valve A Activates Low Bank or Fill Valve A in a one bank dispenser 2 1B Side 1 Valve B Activates the Mid Bank Valve or Fill Valve B in a one bank d...

Страница 44: ...ctions Note Press ENTER to cycle through the different available options Use the numeric keypad to select an option OPTION 1 Program the Unit of Measurement OPTION 2 Decimal Place Configuration OPTION...

Страница 45: ...es Fahrenheit To configure the temperature units in Menu Code 99 follow this procedure 1 To change the temperature unit use the numeric keypad to select an option and press ENTER The display will show...

Страница 46: ...Bennett CNG Spec 100 Series Operators Manual Programming 40 Page Intentionally Left Blank...

Страница 47: ...test is used to display the design type software revision level and the software identification or checksum of this software TO ENTER DIAGNOSTICS FOLLOW THIS PROCEDURE 1 After the correct number 1 or...

Страница 48: ...ersion to version 3 Press ENTER to move to the next level of Diagnostic Code 0 4 Press the CANCEL button to exit this code 5 Press the CANCEL button twice to exit Diagnostics 0 3 819 SOFTWARE I D NUMB...

Страница 49: ...ENTER button to begin The main display and the individual PPM displays begin to display all dashes as shown in Figure 5 6 2 Each time the Enter button is selected a new set of segments will be displa...

Страница 50: ...o exit this test 4 Press the CANCEL button twice to exit Diagnostics DIAGNOSTIC S CODE 4 RAM TEST The RAM test is used to test the system RAM The CPU performs a RAM test to determine if RAM is good or...

Страница 51: ...oblems with power The counters keep track of the number of times a power failure occurs 1 To enter this test enter diagnostics and press the 6 button on the keypad and the ENTER button a The display s...

Страница 52: ...lay shows the dispenser is in Diagnostics Level 6 3 The number of Cold Starts that have occurred appears on the second line of the main display 2 Press the CANCEL button to exit this test 3 Press the...

Страница 53: ...NCEL button twice to exit Diagnostics COUNTER DESCRIPTION CODE TEXT COUNTER DESCRIPTION REASON 6 7 QERR1 Side 1 Modbus Secondary Response Failure Counter Indicates a problem with communication hub met...

Страница 54: ...ANCEL button twice to exit this test 3 Press the CANCEL three times to exit Diagnostics DIAGNOSTIC S CODE 8 LAST SALE LIMIT This code is used to view the sale limit of the last ten sales The last sale...

Страница 55: ...ng 29 Ambient Temp Ambient temperature sensor reporting invalid temperature 2A Target Calculation Target pressure calculation has failed 30 Gas detector 1 is not communicating or it s an A2 alarm stat...

Страница 56: ...Bennett CNG Spec 100 Series Operators Manual Diagnostics 50 Page Intentionally Left Blank...

Страница 57: ...penser Maintenance Schedule and Log Note Follow the suggested maintenance frequency and record results in the maintenance log Keep in a readily accessible location CLEANING PAINTED SURFACES 1 Wash the...

Страница 58: ...Bennett 1218 E Pontaluna Road Spring Lake MI 49456 USA 800 235 7618 Outside USA 231 798 1310 sales bennettpump com www bennettpump com...

Отзывы: