Bennett CNG Spec. 100 Series Operators Manual 

Programming

 

13 

SECTION 4: PROGRAMMING 

The dispenser has a variety of Menu Codes that are accessed by using the Manager’s Keypad. Menu Codes 0, 1, and 2 are accessed by the 
attendant or the manager to read diagnostic error codes or totals. The remaining menu codes are used by first entering an access code in 
Menu Code 3 that can be found on page 15 of this manual. Without the correct access code, the remaining Menu Codes are hidden. 
Please read the description for each Menu Code for complete information on these options. 

Menu Code 

Name 

Description 

Diagnostics 

Diagnostic Tests 

Non-Resettable Totals 

Reading Money, Mass, Number of Sales, Number of Price Changes. 

Totalizer Totals 

View Electro-Mechanical Totals entered in Mode 05 

Manager Access Code 

Entering a four-digit code to access remaining Menu Codes 

Pricing 

Program to set price per mass for each hose and 1 or 2 tier pricing 

Edit Totalizer Value 

Entering a value for each electro-mechanical totalizer (mass total) 

Speed Programming 

Review programming selections or speed program the dispenser 

Pump Type 

Program to set the dispenser type, sides, target pressure, number of grades, hoses, 
tiers, integrated methane detectors, and type of valve 

Decimal Location 

Program to change decimal placement for other than U.S. standard 

No Flow Time Out / Idle 
Authorization Timeout 

Program to set a time for the dispenser to turn off after flow stops and/or program 
the dispenser to turn off after authorized 

10 

End Flow Rate 

Program to control the flowrate at which the dispenser will pause 

11 

Mass Allocation 

Program to control maximum mass of a single sale at one pump 

12 

Timeout Settings 

Program to set the timeout for valve switch delay, last sale timeout, idle timeout 

13 

Audio Tone / Beeper 

Program to set beeper tone options 

14 

PPM Price Display 

Program to set the way price displays operate (Flash, Dash, Flip, Five Digit) 

15 

Fleet Option 

Program to set the fleet system interface compatibility 

18 

Money Totals 

Program to set the money totals calculation method 

21 

Dispenser Communication Type 

Program to set the dispenser in stand-alone or console modes 

22 

Dispenser Address / PLC Address 
/ PLC Low Address 

Program to set the dispenser address, PLC address, and PLC low address 

26 

Shift Totals 

Program to reset shift totals 

27 

Electronic Calibration 

Direct Percent Entry Calibration 

28 

Rounding or Truncating the Sale 
Money 

Program to set rounding or truncate the sale amount 

29 

Resettable Totals 

Entering a value for each meter on the dispenser (mass total) 

35 

Bank Activation to Signal Station 

Program (activate) the bank used to signal the station  

44 

Simulator Mode / Automatic 
Pulse Generation 

Program the simulator for automatic pulse generation 

SIMULATOR USE ONLY!

 

49 

RAM Clear 

Perform a RAM Clear on the equipment 

60 

Training Instruction Prompt 

Program to enable or disable the instruction prompts 

61 

POS Type 

Program to the POS type 

63 

Handle Masking 

Program to determine if the dispenser will report an active handle while not 
authorized 

65 

Max Fill Pressure 

Program to determine the maximum target pressure 

68 

Reported Temperature Units 

Program to adjust the temperature units used when returning readings to the 
station 

80 

Cycle Valves 

Program to manually trigger the solenoid valves 

85 

Process Set Points 

Program to set the input target temperatures and pressure limit 

99 

Unit of Measure 

Program to set the dispenser for mass units, decimal places, temperature units, 
and view E-CAL Values 

 

 

Содержание CNG Spec. 100 Series

Страница 1: ...S MANUAL This manual has important information for safe installation and operation of this equipment Read and understand this manual before applying power Keep this manual and tell all service personn...

Страница 2: ...6050 Facsimile USA 231 799 6202 Email sales bennettpump com or salesintl bennettpump com Website www bennettpump com For new manuals visit our web page at www bennettpump com IMPORTANT Examine the shi...

Страница 3: ...Bennett CNG Spec 100 Series Operators Manual Bennett Limited Warranty i...

Страница 4: ...Bennett CNG Spec 100 Series Operators Manual ii Page Intentionally Left Blank...

Страница 5: ...ttings or Speed Program the Dispenser 17 Menu Code 7 How to Enter the Type of Dispenser 18 Menu Code 8 How to Change the Decimal Point Locations 21 Menu Code 9 How to Set a No Flow Idle Authorization...

Страница 6: ...ic s Code 1 Display Segment Test 43 Diagnostic s Code 2 Error History 43 Diagnostic s Code 3 CPU Test 44 Diagnostic s Code 4 RAM Test 44 Diagnostic s Code 5 Pump Handle Test 45 Diagnostic s Code 6 Cou...

Страница 7: ...ally every 3 years to ensure safe operation of the vehicle or cylinder manufacture To prevent electric shock keep the electrical parts of the dispenser dry Electronic components are static sensitive U...

Страница 8: ...aintenance of Compressed Natural Gas Vehicle Fueling Facilities UNAUTHORIZED ALTERATION OF BENNETT PRODUCTS DANGER BEFORE PERFORMING ANY TYPE OF SERVICE TO THE DISPENSERS BE SURE TO SHUT OFF ALL ELECT...

Страница 9: ...tablished by the American with Disabilities Act ADA per Chapter 3 Building Blocks Section 308 Reach Ranges and Section 309 Operable Parts The forward and side reach maximum height is 48 inches above t...

Страница 10: ...Bennett CNG Spec 100 Series Operators Manual Safety Information 4 Page Intentionally Left Blank...

Страница 11: ...se width x depth INSIDE 43 3 8 width x 15 1 8 depth OUTSIDE 44 width x 19 depth CNG Series Estimated Shipping Weight pounds GGE 650 lbs 295 kg ENVIRONMENTAL REQUIREMENTS Operating and Storage Temperat...

Страница 12: ...ollowing section provides a description of the controls and instrumentation used on a CNG Spec 100 Dispenser Note Not all dispenser options are shown in Figure 2 1 below FIGURE 2 1 DISPENSER LAYOUT Up...

Страница 13: ...fore and during the fueling process The idle screen shown in Figure 2 2 is an example of how of the module prompts the user with guided instructions Note The display is controlled by the POS Refer to...

Страница 14: ...iagnostics section for complete instructions for using the keypad to read error codes AC OFF MESSAGE The AC OFF message occurs whenever the power has been interrupted or turned off to the dispenser If...

Страница 15: ...vehicle and hang it up in the nozzle boot ending the transaction HOW TO READ THE ELECTRO MECHANICAL TOTALIZER NOTE Because of rounding methods used and the nature of electronic totals versus an analo...

Страница 16: ...Totals with the Magnetic Reed Switch Press the Up Arrow to move through product x totals money mass sale price counters Press ENTER to move from product x to product y TO READ THE MONEY TOTALS ON THE...

Страница 17: ...over 2 Tap the magnet over the mass display print again to read the Mass Totals for Product 1 P12 1 is displayed in the PPM display to indicate the first Mass Total for Product 1 as shown in Figure 3...

Страница 18: ...THIS PROCEDURE 1 Press the 2 button and then the MODE button on the keypad a The main display shows the electro mechanical total as shown in Figure 3 9 b The total number is carried to three decimal p...

Страница 19: ...single sale at one pump 12 Timeout Settings Program to set the timeout for valve switch delay last sale timeout idle timeout 13 Audio Tone Beeper Program to set beeper tone options 14 PPM Price Displa...

Страница 20: ...Instruction Prompt 1 Enabled 63 Handle Masking 0 Disabled 65 Max Fill Pressure P30 3300 P36 4000 Default value based on the grade type selected in mode 7 68 Reported Temperature Units 1 Fahrenheit 80...

Страница 21: ...efore the remaining protected menus can be accessed The display shown in Figure 4 2 appears when the cancel button is pressed HOW TO CHANGE THE 4 DIGIT MANAGER S ACCESS CODE CAUTION To avoid having to...

Страница 22: ...before this mode may be entered NOTE The Price Per Mass reflected in these figures represent a setup with 2 Tier Pricing TO PROGRAM PRICE PER MASS DATA FOLLOW THIS PROCEDURE 1 Press the 4 button and t...

Страница 23: ...chanical totalizers When the first new number is pressed the mass displays zeros and begins rotating the new total into the display 3 Press the ENTER button to save the new value 4 Press the CANCEL bu...

Страница 24: ...icates a gas detector is present with Modbus Slave ID of 2 or 3 0 None Default 1 Add2 2 Add3 3 Both TYPE OF VALVE 1 Solenoid Default 2 Ball TO ENTER DISPENSER CONFIGURATION FOLLOW THIS PROCEDURE To re...

Страница 25: ...or 1 Grade as shown in Figure 4 12 3 If necessary enter the recommended default setting for number of grades using the numeric keypad This option will only accept the options listed above Note If an e...

Страница 26: ...option will only accept the options listed above Note If an error is made press the correct number The new number replaces the error 4 Press ENTER to save setting and to advance to the next option If...

Страница 27: ...the PPM display can be changed Contact an authorized service technician to change from gallons to liters The dispenser is shipped from the factory set for the monetary system in the United States NOT...

Страница 28: ...ade press the 0 button until all three digits are zeros and enter a new number or push the number buttons until the correct number of seconds appears in the mass display NOTE If a 0 is entered in this...

Страница 29: ...10 FOLLOW THIS PROCEDURE 1 After the Menu Code has been accessed press the number 1 and 0 button and then the MODE button on the keypad The main display on an un programmed dispenser will appear as i...

Страница 30: ...s or checking the flow end connections The default timeout is 3 seconds and the maximum timeout is 99 seconds TO PROGRAM THE AMOUNT OF TIME THAT THE VALVE DELAYS IS SHOWN ON THE MAIN DISPLAY FOLLOW TH...

Страница 31: ...he dispenser can be programmed to emit audio tones when certain buttons are pushed or a pump handle is turned on The four options available are 0 No audio tones 1 Audio tone whenever a button on the k...

Страница 32: ...display and cash to the top display requiring FLIP to be turned on Digit Is used to program the dispenser for a four or five digit PPM display 0 Four Digit Display 1 default Five Digit Display Note If...

Страница 33: ...ALS CALCULATION METHOD Menu Code 18 allows the manager to select the method for calculating money totals The first method adds the value on the display to the Money Totals and stores the amount This M...

Страница 34: ...s are on the same communication loop If more than one dispenser is using the same communications loop up to four dispensers To review or change the settings in Manager s Mode 22 press the ENTER button...

Страница 35: ...xit mode 22 PLC LOWEST ADDRESS This option is used to enter the lowest PLC address sent by the PLC if applicable The dispenser needs to know the lowest address sent by the PLC so the dispenser can ver...

Страница 36: ...amount For example if the total money amount for the dispenser is 7 890 123 45 the display appears as in Figure 4 39 b The PPM display window reads P1 1 d for Product 1 Money Total 2 To read the money...

Страница 37: ...ss the button as shown in Figure 4 43 Remember only the number of products selected in Menu Code 7 will be displayed CAUTION THE FOLLOWING PROCEDURE ZEROS ALL THE SHIFT MONEY MASS AND COUNTER TOTALS I...

Страница 38: ...up arrow button or the down arrow button to view the current electronic calibration correction constant for each configured meter product A or product B Once you are viewing the desired meter press E...

Страница 39: ...e MENU CODE 29 HOW TO SET THE RESETTABLE ELECTRONIC MASS TOTALS Menu Code 29 is used to reset the electronic resettable meter totals that accumulate in the dispenser every time a sale is completed Thi...

Страница 40: ...MENU CODE 44 SIMULATOR MODE CAUTION THIS PROCEDURE IS ONLY TO BE USED FOR TROUBLESHOOTING CONTACT BENNETT TECHNICAL SUPPORT PRIOR TO ENTERING THIS MODE IMPORTANT THE CALIBRATION SWITCH MUST BE UNSEAL...

Страница 41: ...s keypad was plugged in for the first time as shown in Figure 4 57 The password in Mode 03 will need to be re entered before proceeding MENU CODE 60 HOW TO SET THE INSTRUCTION PROMPT Menu Code 60 is...

Страница 42: ...d 3 then the MODE button on the keypad The PPM display shows the dispenser is in Menu Code 61 If the dispenser has not been programmed since it came from the factory the number 0 appears in the main d...

Страница 43: ...binet VALVE OPTIONS 0 Off All Valves Off 1 1A Side 1 Valve A Activates Low Bank or Fill Valve A in a one bank dispenser 2 1B Side 1 Valve B Activates the Mid Bank Valve or Fill Valve B in a one bank d...

Страница 44: ...ctions Note Press ENTER to cycle through the different available options Use the numeric keypad to select an option OPTION 1 Program the Unit of Measurement OPTION 2 Decimal Place Configuration OPTION...

Страница 45: ...es Fahrenheit To configure the temperature units in Menu Code 99 follow this procedure 1 To change the temperature unit use the numeric keypad to select an option and press ENTER The display will show...

Страница 46: ...Bennett CNG Spec 100 Series Operators Manual Programming 40 Page Intentionally Left Blank...

Страница 47: ...test is used to display the design type software revision level and the software identification or checksum of this software TO ENTER DIAGNOSTICS FOLLOW THIS PROCEDURE 1 After the correct number 1 or...

Страница 48: ...ersion to version 3 Press ENTER to move to the next level of Diagnostic Code 0 4 Press the CANCEL button to exit this code 5 Press the CANCEL button twice to exit Diagnostics 0 3 819 SOFTWARE I D NUMB...

Страница 49: ...ENTER button to begin The main display and the individual PPM displays begin to display all dashes as shown in Figure 5 6 2 Each time the Enter button is selected a new set of segments will be displa...

Страница 50: ...o exit this test 4 Press the CANCEL button twice to exit Diagnostics DIAGNOSTIC S CODE 4 RAM TEST The RAM test is used to test the system RAM The CPU performs a RAM test to determine if RAM is good or...

Страница 51: ...oblems with power The counters keep track of the number of times a power failure occurs 1 To enter this test enter diagnostics and press the 6 button on the keypad and the ENTER button a The display s...

Страница 52: ...lay shows the dispenser is in Diagnostics Level 6 3 The number of Cold Starts that have occurred appears on the second line of the main display 2 Press the CANCEL button to exit this test 3 Press the...

Страница 53: ...NCEL button twice to exit Diagnostics COUNTER DESCRIPTION CODE TEXT COUNTER DESCRIPTION REASON 6 7 QERR1 Side 1 Modbus Secondary Response Failure Counter Indicates a problem with communication hub met...

Страница 54: ...ANCEL button twice to exit this test 3 Press the CANCEL three times to exit Diagnostics DIAGNOSTIC S CODE 8 LAST SALE LIMIT This code is used to view the sale limit of the last ten sales The last sale...

Страница 55: ...ng 29 Ambient Temp Ambient temperature sensor reporting invalid temperature 2A Target Calculation Target pressure calculation has failed 30 Gas detector 1 is not communicating or it s an A2 alarm stat...

Страница 56: ...Bennett CNG Spec 100 Series Operators Manual Diagnostics 50 Page Intentionally Left Blank...

Страница 57: ...penser Maintenance Schedule and Log Note Follow the suggested maintenance frequency and record results in the maintenance log Keep in a readily accessible location CLEANING PAINTED SURFACES 1 Wash the...

Страница 58: ...Bennett 1218 E Pontaluna Road Spring Lake MI 49456 USA 800 235 7618 Outside USA 231 798 1310 sales bennettpump com www bennettpump com...

Отзывы: