Bennett CNG Spec. 100 Series Operators Manual
Programming
20
TYPE OF GRADE (TARGET PRESSURE)
This option is used to select the target pressure. This option is set at the factory. The default setting will appear in the Main Display.
1 = P30
2 = P36 (Default)
1.
Once
Enter
has been pressed from the previous option, the grade type will appear in
the main display.
2.
The default setting is for P36 (3,600) as shown in
Figure 4.14
.
3.
If necessary, enter the recommended default setting for
grades
(target pressure)
using
the numeric keypad. This option will only accept the options listed above.
Note
: If an error is made, press the correct number. The new number replaces the
error.
4.
Press [
ENTER
] to save setting and to advance to the next option. If programming is
complete, press [
CANCEL
] button to exit this menu option.
5.
Press the [
CANCEL
] button again to exit mode 7.
NUMBER OF TIERS
This option is used to select the number of tiers used. This option is set at the factory. The default setting will appear in the Main Display.
1 = 1 Tier (Default)
2 = 2 Tier
1.
Once
Enter
has been pressed from the previous option, the number of tiers will
appear in the main display.
2.
The default setting is for 1-Tier as shown in
Figure 4.15
.
3.
If necessary, enter the recommended default setting for
number of tiers
using the
numeric keypad. This option will only accept the options listed above.
Note
: If an error is made, press the correct number. The new number replaces the
error.
4.
Press [
ENTER]
to save setting and to advance to the next option. If programming is
complete, press [
CANCEL]
button to exit this menu option.
5.
Press the [
CANCEL
] button again to exit mode 7.
NUMBER OF DETECTORS
This option is used to select the number of detectors used. This option is set at the factory. The default setting will appear in the Main
Display.
Note:
Add2 indicates a detector is present with Modbus Slave ID of 2 and Add3 indicates a detector is present with Modbus Slave
ID of 3.
0 = None (Default)
1 = Add2
2 = Add3
1.
Once
Enter
has been pressed from the previous option, the number of detectors will
appear in the main display.
2.
The default setting is set to 0-None indicating that a detector is not present as shown
in
Figure 4.16
.
3.
To change the default setting, use the numeric keypad to select the desired option.
Add2 indicates a detector is present with Modbus Slave ID of 2 and Add3 indicates a
detector is present with Modbus Slave ID of 3.
Note
: If an error is made, press the
correct number. The new number replaces the error.
4.
Press [
ENTER
] to save setting and to advance to the next option. If programming is
complete, press [
CANCEL
] button to exit this menu option.
5.
Press the [
CANCEL
] button again to exit mode 7.
FIGURE 4.16 – DETECTORS
FIGURE 4.15 - TIER
Sale $
Tier
GGE
1
code
-- 7
Sale $
Detect
GGE
0
code
-- 7
FIGURE 4.14 – GRADES (TARGET PRESSURE)
Sale $
Press
GGE
P36
code
-- 7
Содержание CNG Spec. 100 Series
Страница 3: ...Bennett CNG Spec 100 Series Operators Manual Bennett Limited Warranty i...
Страница 4: ...Bennett CNG Spec 100 Series Operators Manual ii Page Intentionally Left Blank...
Страница 10: ...Bennett CNG Spec 100 Series Operators Manual Safety Information 4 Page Intentionally Left Blank...
Страница 46: ...Bennett CNG Spec 100 Series Operators Manual Programming 40 Page Intentionally Left Blank...
Страница 56: ...Bennett CNG Spec 100 Series Operators Manual Diagnostics 50 Page Intentionally Left Blank...