iso415R-x_D00401_00_M_XXEN / 04.2021 23
ISOMETER® iso415R
Address
(dec)
Register name
Data type Bytes Mode
Value/Unit/Comment
Factory
setting
3008
Response value R
an1
_ext
Uint16
2
RO
10…1000 [kΩ], the last response value stored via
the interface
40 k
Ω
3009
Response value R
an2
_ext
Uint16
2
RO
5…700 [kΩ], the last response value stored via
the interface
10 k
Ω
Modbus RTU parameters (32000
…
32099)
32000
Device address
Uint16
2
RW
1…247
Last 2 digits
of the serial
100
32001
Baud rate
Uint32
4
RW
9600, 19200, 38400, 57600, 115200
19200
32003
Parity
Uint16
2
RW
1 = even
2 = odd
3 = none
1
32004
Stop bits
Uint16
2
RW
1 = 1
2 = 2
3 = automatic
3
32006
Update permission
Uint16
2
RW
0 = SW update via Modbus RTU not permitted
1 = SW update via Modbus RTU permitted
0
32007
Write access
Uint16
2
RW
1 = Write access enabled
2 = Write access disabled
CAUTION! Writing of all parameters is disabled,
enabling is only possible via the T/R button!!!"
1
Relay (32100
…
32199)
32100
Relay mode
Uint16
2
RW
1 = NO principle
2 = NC principle
2
32101
Alarm assignment test
Uint16
2
RW
0 = Disabled
1 = Enabled
1
32102
Alarm assignment
device error
Uint16
2
RW
0 = Disabled
1 = Enabled
1
32103
Alarm assignment
prewarning R
an1
Uint16
2
RW
0 = Disabled
1 = Enabled
0
32104
Alarm assignment
main alarm R
an2
Uint16
2
RW
0 = Disabled
1 = Enabled
1
32105
Alarm assignment -
connection fault E/KE
Uint16
2
RW
0 = Disabled
1 = Enabled
1
32106
Alarm assignment -
connection fault L1/L2
Uint16
2
RW
0 = Disabled
1 = Enabled
1
32107
Alarm assignment
Max. C
e
/fault
Uint16
2
RW
0 = Disabled
1 = Enabled
1
Response values (33000…33099)
33000
Response value
prewarning R
an1
Uint16
2
RW
10…1000 [kΩ], step size 1 kΩ, writing is only
possible when R
an1
potentiometer is set to "Ext"
40 kΩ
33001
Response value
main alarm R
an2
Uint16
2
RW
5…700 [kΩ], step size 1 kΩ, writing is only possi-
ble when R
an2
potentiometer is set to "Ext"
10 kΩ
Содержание ISOMETER iso415R
Страница 30: ...30 iso415R x_D00401_00_M_XXEN 04 2021 ...
Страница 31: ...iso415R x_D00401_00_M_XXEN 04 2021 31 ISOMETER iso415R ...