iso415R-x_D00401_00_M_XXEN / 04.2021 25
ISOMETER® iso415R
Address
(dec)
Register name
Data type Bytes Mode
Value/Unit/Comment
Factory
setting
Control commands (60000
)
60000 Function selection
Uint16
2
WO
Function selection register to control the
function of the following registers. Only
specified values are permitted.
2 = Find device
4 = Reset to factory settings /
Reset parameters
6 = Test
7 = Reset
N/A
Function 2: Find device
60000 Function selection
Uint16
2
WO
2
→
Selection of the "Find device"
function
N/A
60001 Pattern value part 1
Uint16
2
W0
61918
→
Safety pattern must be written
for the function to be executed
N/A
60002 Pattern value part 2
Uint16
2
W0
0
→
Safety pattern must be written for the
function to be executed.
N/A
60003 Period
Uint16
2
W0
0…300
→
Period in seconds during which
the device lights up. If the device receives
the value "0", the function is stopped.
N/A
Function 4: Reset to factory settings/Reset parameters
60000 Function selection
Uint16
2
WO
4
→
Selection of "Reset to factory
settings/Reset parameters" function
N/A
60001 Pattern value part 1
Uint16
2
WO
64199
→
Safety pattern must be written
for the function to be executed
N/A
60002 Pattern value part 2
Uint16
2
WO
1304
→
Safety pattern must be written for
the function to be executed
N/A
60003 Type of reset
Uint16
2
WO
1
→
Reset to factory settings including
interface parameters
2
→
Reset to factory settings excluding
interface parameters
N/A
Function 6: Test
60000 Function selection
Uint16
2
WO
6
→
Selection of the "Test" function
N/A
60001 Pattern value part 1
Uint16
2
WO
32343 --> Safety pattern must be written
for the function to be executed
N/A
60002 Pattern value part 2
Uint16
2
WO
0
→
Safety pattern must be written for the
function to be executed
N/A
60003 Type of test
Uint16
2
WO
1
→
Start IMD test
N/A