iso415R-x_D00401_00_M_XXEN / 04.2021 21
ISOMETER® iso415R
5
Modbus settings
5.1
Overview
Description of the Modbus registers for iso415R devices. The following Modbus function codes
are supported:
•
Holding register for reading out values
(Read Holding Register; function code 0x03)
•
Register for device programming
(Write Multiple Registers; function code 0x10)
For a complete Modbus protocol specification, visit http://www.modbus.org.
5.1.1 Read and write accesses
RO
READ ONLY (read access only)
RW
READ/WRITE (read and write access)
WO
WRITE ONLY (write access only)
5.1.2 Data types
Float
IEEE754 32-bit (single precision floating point number)
Int16
Signed 16-bit integer
Int32
Signed 32-bit integer
Uint16
Unsigned 16-bit integer
Uint32
Unsigned 32-bit integer
String UTF8
ASCII character string
5.1.3 Register areas
Range
Start address End address
Info
0
99
Measurement status
999
3999
Alarm status
2000
2999
Range
3000
3999
Modbus RTU parameters
32000
32099
Relay parameters
32100
32199
Range
Start address End address
Response value parameters
33000
33399
Monitoring parameters
33400
33499
Device error status
58000
58099
Interface parameters
59000
59099
Control commands
60000
60004