Modbus settings
Address
(dec)
Register name
Data type Bytes Mode
Value/Unit/Comment
Factory
setting
Function 7: Reset
60000 Function selection
Uint16
2
WO
7
→
Selection of "Reset" function
N/A
60001 Pattern value part 1
Uint16
2
WO
13623
→
Safety pattern must be written
for the function to be executed
N/A
60002 Pattern value part 2
Uint16
2
WO
0
→
Safety pattern must be written for the
function to be executed
N/A
60003 Type of reset
Uint16
2
WO
1
→
Reset of the alarm message when
fault memory is enabled
N/A