Commissioning
Commissioning
iso1685DP_D00272_02_M_XXEN/07.2017
27
6.3.5 Setting response value
R
an2
for Alarm 2
The response value for the main alarm can be set here.
A value of 50 Ω/V is recommended for the main alarm.
6.3.6 Setting EDS mode
Set the mode for the insulation fault location to manual, automatic or 1 cycle. For further
information, refer to
.
6.3.7 Set the EDS current
Set the maximum locating current.
EDS441: 1-5mA
EDS440: 10-50mA
For further information see
Alarm 2
6.6.7
10
kΩ
min.
max.
200Ω
1MΩ
lle
6.6
6/9
Commissioning
Please set the
response value
for R(an2) for
Alarm2.
Mode
o off
o
manually
•
auto
o
1cycle
6.6.8
lle
Commissioning
6.6
Please select
the EDS mode.
7/9
Mode
o off
o
manually
•
auto
o
1cycle
6.6.8
lle
Commissioning
6.6
Please set the
required EDS
current.
8/9
6.3.8 TEST
Set the mode for the insulation fault location to manual, automatic or 1 cycle. For further
information, refer to
.
6. 4 Recommissioning
If the device has already been put into operation before, the self test will be started short-
ly after the supply voltage has been connected. You can restart the commissioning wiz-
ard using the following menu path:
Menu/Device settings/Commissioning
This menu can be used to modify previously made settings.
If the device has been commissioned before, the self test is not run again. It can be called
up via the "Control" menu (
refer to
).
Observe device status!
Once initial commissioning has been completed and the initial measure-
ment taken, the device changes from the alarm state to normal state by
adhering to the set response values.
lle
TEST
6.6.10
Start Test?
Relais may
switch.
Cancel
TEST