Settings
Settings
iso1685DP_D00272_02_M_XXEN/07.2017
39
9.1
(6.3) Interface
Set the parameters for connection of other devices to the ISOMETER® in the interface
menu:
9.1
(6.3.1) BMS
Set the parameters for communication with other devices via the BMS bus.
9.1
(6.3.1.1) BMS address
Select an address between 1 and 90 for the BMS bus.
9.1
(6.4) Display
Adjust the display brightness for the ISOMETER® in the display menu:
9.1
(6.4.1) Brightness
Adjust the display brightness between 0 % and 100 % in steps of 10.
If no button is pressed on the display for 15 minutes, the brightness of the display will be
reduced. If now a button is pressed, the normal brightness is restored.
9.1
(6.5) Password
Use the password function to protect the device parameters against unauthorised adjust-
ment. The default password is 0000.
9.1
(6.5.1) Password
Enter an individual four-digit password.
9.1
(6.5.2) Status
Decide whether the password query should be used:
•on
Password query active
•off
Password query inactive
9.1
(6.6) Commissioning
In the commissioning menu, you can open the ISOMETER®'s commissioning wizard again.
9.1
(6.7) Service
The service menu can only be accessed by Bender service staff.
9.1
7.0 Info
The ISOMETER®'s current settings can be viewed in the Info menu. Navigate through the
different views using the and buttons:
•Info - Device
Device name, serial number, article number
•Info - Software
Software version measurement technique,
software version HMI
•Info - Measurement
technique
Set profile, locating current and EDS mode
•Info - Clock
Time, date, summer time
•Info - BMS
Address of the RS-485 interface