Commissioning
Commissioning
iso1685DP_D00272_02_M_XXEN/07.2017
26
6.3 Initial commissioning
Follow the instructions of the commissioning wizard on the display.
Use the device buttons to navigate. For a description of the device buttons,
refer to
6.3.1 Setting the language
The language selected here will be used in the menu and for device messages.
6.3.2 Setting date and time
Alarm messages in the history memory and the insulation resistance value over time can
only be assigned correctly to the isoGraph when date and time are set correctly.
Language
6.6.2
• Deutsch
o English
o ...
Date 6.6.3
14.08.2016
min.
1
max.
31
lle
Commissioning
6.6
Please set the
current date
and time.
2/9
6.3.3 Setting the profile
In order to optimally adapt the insulation monitoring device to the system to be moni-
tored, select a profile here that suits your system. For an overview of the profiles, refer to
“Device profiles” auf Seite 46
. The profile Power circuits is suitable for most IT systems.
6.3.4 Setting response value
R
an1
for Alarm 1
You can set the prewarning response value here.
The response value range changes depending on the selected profile. Re-
fer to
“Response values for insulation monitoring” auf Seite 54
.
Profile
6.6.5
• Power circuits
o Control circuits
o Inverter>10 Hz
o Inverter<10 Hz
o Fast 2000 μF
lle
Commissioning
6.6
Please select a
profile that
suits your
application.
4/9
Alarm 1
6.6.6
40
kΩ
min. 200Ω
max.
1MΩ
lle
Commissioning
6.6
Please set the
response value
for R(an1) for
Alarm1.
5/9