Device communication via the BMS bus
Device communication via the BMS bus
iso1685DP_D00272_02_M_XXEN/07.2017
44
10.7.4 Error codes
The following list contains all relevant error codes output via the BMS bus. The right-hand
column describes the relevant action to be taken in each case.
BMS
error code
Components
Fault
Action
0.30
Connection
Connection earth (E/KE)
Check connection
0.40
Connection
Connection system (L1/+, L2/–)
Check connection
4.05
Parameter
Incorrect measurement method
selected
Change measure-
ment method
7.63
System
Timeout system management
Restart the device
8.11
Hardware
Self test insulation measurement
Contact service
8.12
Hardware
Hardware measuring voltage source
Replace device
8.31
Hardware
PGH: locating current too high
Replace device
8.32
Hardware
PGH: locating current cannot be
switched off
Replace device
8.42
Hardware
Supply voltage ADC
Replace device
8.43
Hardware
Supply v12 V
Replace device
8.44
Hardware
Supply voltage –12 V
Replace device
8.45
Hardware
Supply v5 V
Replace device
8.46
Hardware
Supply v3.3 V
Replace device
9.61
Parameters
Insulation measurement
Load factory settings
and set parameters
again
9.63
Parameters
Locating current injector
Load factory settings
and set parameters
again
9.64
Parameters
Voltage measurement
Contact service
9.70
System
General software error
Restart the device
9.71
System
Control flow
Restart the device
9.72
System
Programme sequence insulation
measurement
Restart the device
9.74
System
Programme sequence locating current
injector
Restart the device
9.75
System
Programme sequence voltage meas-
urement
Restart the device
9.76
System
Programme sequence temperature
measurement
Restart the device
9.77
System
Programme sequence history memory Restart the device
9.78
System
Programme sequence console
Restart the device
9.79
System
Programme sequence self test
Restart the device
9.80
System
Stack error
Restart the device
9.81
System
Internal programme sequence
Restart the device
9.82
System
Internal programme sequence
Restart the device
BMS
error code
Components
Fault
Action
Содержание ISOMETER iso1685DP