Settings
Settings
iso1685DP_D00272_02_M_XXEN/07.2017
40
9.2 Factory settings
Response values, alarms and profile
Switching elements
Insulation fault location
Parameter
Value
Status
Measurement method
Power circuits
Insulation response value
R
an1
40kΩ
Insulation response value
R
an2
10kΩ
Fault memory
off
Coupling monitoring
on
Parameter
Value
Status
Relay 1 (11/12/14)
Operating mode: N/C operation
Function: Insulation measurement
Relay 2 (21/22/24)
Operating mode: N/C operation
Function: Insulation measurement
Relay 3 (31/32/34)
Operating mode: N/C operation
Function: Device error
Parameter
Value
Status
EDS mode
auto
PGH current
25 mA
BMS
Digital inputs
Other
Parameter
Value
Status
BMS address
2
BMS termination
ON
Parameter
Value
Status
Digital input 1
Mode (operating mode): active high
Function: Test
Digital input 2
Mode (operating mode): active high
Function: standby
Parameter
Value
Status
Standby mode (disconnection from the
mains)
off
Permissible system leakage capacitance
depending on the set measurement method
(refer to
Buzzer
off
Menu language
German
Password query
off
Password
0000