![Bender ATICS-2-63A-ISO Скачать руководство пользователя страница 78](http://html1.mh-extra.com/html/bender/atics-2-63a-iso/atics-2-63a-iso_manual_2731578078.webp)
78
ATICS-2-ISO_D00046_04_M_XXEN / 03.2021
Menu mode: Operation and setting
Set the device address for the connection to the internal BMS bus. Change the device address con-
cerned when several devices are connected to one BMS bus. One device (e.g. MK800) must have ad-
dress 1 (master). All other devices are addressed in consecutive order: 2,3,4…. There should be no gaps
between the addresses. This is the only way to ensure the function of the system.
Menu
Description
Exit
Exit settings menu "Interface"; go up one menu level
1. Address
Setting range:
2…90
2. Settings
on
Allow settings to be changed via interface
(e.g. a COM465… Ethernet gateway)
off
Do not allow settings to be changed via interface
3. TEST
on
Allow a test to be carried out via interface (e.g. a COM465…
Ethernet
gateway)
off
Do not allow a test to be carried out via interface
4. Failure monitoring
on
Reports when no (more) communication with the BMS master is
detected.
off
It is not monitored whether a BMS master is present. This setting
is required when ATICS® is used as a "Stand-alone" device without BMS master.
I
D
anger
!
When this setting is selected, the conditions for functional sa-
fety (SIL2) are no longer met.
I
W
arning
!
No EDS functionality is possible if this settings has been selec-
ted.
I
C
aution
!
In the event of a power failure of more than eight hours, the
time and date will be reset to the factory settings.
If the "Clock" setting is
not corrected, all functions depending on this setting (history memory,
logger, test interval, service interval...) will lead to unusable results.
5. Profile
Stand.
Standard setting for channel assignment for alarms/measured values and
BMS channels
TEST
Alternative setting (see P. 46 and P. 63)
7.3.4.10 Settings menu 10: Clock
Time and date are required for displays in the "History/Loggers" menu. The time setting is synchronised
via the BMS bus. The device with address 1 (MK800, MK2430, CP9xx or TM…) synchronises all other de-
vices every hour.
The time setting for the ATICS® is required for the rare case of use without a BMS bus. In this case,
ATICS® displays the fault message "No master". The date format, date and time can be set. These set-
tings remain stored for approx. eight hours following a supply interruption. The date and time will then
be reset to the factory settings (01.01.2010, 00:00:00).
Содержание ATICS-2-63A-ISO
Страница 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Страница 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Страница 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Страница 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Страница 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...
Страница 100: ...100 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Technical data 10 2 T V test report according to VDE 0100 Part 710...
Страница 101: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 101 ATICS 2 63A ISO 10 3 T V certificate regarding functional safety...