Menu mode: Operation and setting
Selecting a line:
1. Use the " " arrow button to go to the line setting. Press the " " button.
2. Use the arrow buttons to select one line (voltage 1, 2) or both lines (voltage 1…2). Press the "
" button to confirm your selection.
Setting voltage for one line:
Setting voltage for both lines:
Adjusting the settings:
Menu
Description
Exit
Exit settings menu "Voltage"; go up one menu level
1. Undervolt.
Undervoltage; setting range:
160…207 V (278 V…360 V)*
2. Overvolt.
Overvoltage; setting range:
240…275 V (417 V…478 V)*
3. t(on)
Response delay**:
Setting range:
50 ms…100 s
Resolution of settings:
50 ms / 100 ms / 1 s / 5 s / 10 s
4. t(off)
Delay on release**:
Setting range:
200 ms…100 s
Resolution of settings:
50 ms / 100 ms / 1 s / 5 s / 10 s
5. Hysteresis
Setting range:
2…10 %
Resolution of setting:
1 %
* Values for ATICS…400 versions
** Observe also the time diagrams
7.3.4.3 Settings menu 3: Current
In this menu, you can adjust settings for current monitoring (short-circuit detection) downstream of the
transfer switching and monitoring device (TN system). The current is detected via a measuring current
transformer (T3 in the connection example P. 33).
Voltage:
1 . . 2
Exit
1. Undervolt.:
184V
2. Overvoltage:
250V
Voltage:
2
Exit
1. Undervolt.:
184V
2. Overvoltage.
250V
Содержание ATICS-2-63A-ISO
Страница 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Страница 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Страница 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Страница 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Страница 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...
Страница 100: ...100 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Technical data 10 2 T V test report according to VDE 0100 Part 710...
Страница 101: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 101 ATICS 2 63A ISO 10 3 T V certificate regarding functional safety...