ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 31
ATICS-2-63A-ISO
4.2.2 Connecting the ATICS® safely
I
r
isk
of electrocution due to electric shock!
If any of the supplies are switched on, some of the system parts which are not yet fully installed may
be live.
Preventing unintended switch-on:
• Open the transparent cover
• Wait until "manual mode" appears on the display
• Set to switch position "0" using the Allen key
• Lock the device using a padlock
I
r
isk
of electrocution due to electric shock!
Connecting wires can come loose and fall out if the ferrules being used are too short, the wire ends
are tinned or the connection screws have not been tightened enough.
Consider a stripping length of 20 mm and do not use ferrules when connecting lines 1, 2 and 3.
Observe assignment of "ATICS® terminals". Note especially that the two supplies are always connec-
ted to the device from the top. Use a torque wrench to tighten the terminal screws. Check all the
screws on a regular basis to make sure they are seated tightly.
I
D
anger
!
Caution when operating the " -ES" version of ATICS® without the external ATICS-ES ener-
gy storage device!
The enclosed dummy plug must be plugged into the energy storage device connection of the ATICS®
as soon as no ATICS-ES is connected. This dummy plug (A370261) is used for touch protection
against hazardous voltages.
I
C
aution
:
Incorrect insulation measurement possible.
The ATICS® contains an insulation monitoring device. If another insulation monitoring device is con-
nected, the devices will affect one another. This will lead to false measurements. Therefore, only con-
nect one insulation monitoring device in each interconnected IT system!
I
r
isk
of destruction!
• While insulation and voltage tests are carried out. Disconnect the device from the mains for the du-
ration of the test.
• If connected incorrectly. The terminals labelled GND must not be connected to PE.
Содержание ATICS-2-63A-ISO
Страница 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Страница 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Страница 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Страница 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Страница 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...
Страница 100: ...100 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Technical data 10 2 T V test report according to VDE 0100 Part 710...
Страница 101: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 101 ATICS 2 63A ISO 10 3 T V certificate regarding functional safety...