ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 71
ATICS-2-63A-ISO
Menu
Description
Exit
Exit settings menu "Current"; go up one menu level
1. Mode
on
Current monitoring enabled
off
No current monitoring
2. transformer
STW3
Bender measuring current transformer STW3
STW4
Bender measuring current transformer STW4
3. CT monitoring.
on
CT connection monitoring enabled
off
CT connection monitoring disabled
Note:
External interference from loads can cause false tripping. In this case, the func-
tion has to be disabled. The functional safety of the transfer switching device is in no
way impaired by this.
7.3.4.4 Settings menu 4: IT system
In this menu, you can adjust settings for IT system monitoring.
Menu
Description
Exit
Exit settings menu "IT system"; go up one menu level
1. Insulation
Setting range:
50…250 kΩ
Resolution of setting: starting at 5 kΩ
2. Current trans-
former
Measuring current transformer T4 in the connection example P. 33
STW2
Measuring current transformer
STW3
Measuring current transformer
SWL
Split-core type measuring current transformer
3. CT monitoring.
on
CT connection monitoring enabled
off
CT connection monitoring disabled
Note:
External interference from loads can cause false tripping. In this case, the function
has to be disabled. The functional safety of the transfer switching device is in no way
impaired by this.
4. Load
Setting range:
5…50 A (STW2), 5…100 A (STW3, SWL)
Resolution of setting: 1 A, IT system
Setting values:
Transformer
3150 VA 4000 VA 5000 VA 6300 VA 8000 VA 10 000 VA
Setting
14 A
18 A
22 A
28 A
35 A
45 A
5. Hysteresis
Setting range:
5…30 %
Resolution of setting: 1 %
The setting only affects the value of the load current.
6. t(on)
Response delay load:
Setting range:
0 s…100 s
Resolution of setting: 1 s
Содержание ATICS-2-63A-ISO
Страница 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Страница 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Страница 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Страница 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Страница 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...
Страница 100: ...100 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Technical data 10 2 T V test report according to VDE 0100 Part 710...
Страница 101: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 101 ATICS 2 63A ISO 10 3 T V certificate regarding functional safety...