Menu mode: Operation and setting
Menu
Description
12. Temperature
on
Relay switches in the event of overtemperature in the IT system
transformer
off
13. Undervolt.
on
Relay switches in the event of undervoltage at the ATICS® output
(line 3)
off
i
The reminders for the test (7. Test interval) or the service (8. Serviceinterv) are
always triggered at 12:00 pm. If these messages appear at night, the time is set incorrectly on the de-
vice.
7.3.4.6 Settings menu 6: Dig. input
In this menu, you can adjust settings for the mode of operation and function of the digital input. The
digital input is electrically isolated. It is designed for an input of AC/DC 24 V. ATICS-2-ISO has a digital
input and a relay output with a changeover contact.
For the input, selection is possible when the input is set to: "24V" (high) or "0V" (low). In the "24V" set-
ting, the selected function (e.g. alarm message) is carried out when there are 24 volts there. In the "0V"
setting, the selected function is carried out when there are 0 volts there. It is for this reason that you
should always set unused digital inputs to "off".
i
By selecting the function of the digital input, the recommended response value is automatically ad-
justed:
- Test, M/A,1, 0, 2 (switch positions)
24V (cannot be changed)
- no2->1, 1<->2, bypass, alarm and OPL
0 V (can be changed)
The "Bypass" setting can only be changed temporarily for test purposes. After restarting the ATICS®
this setting returns to "0V"!
Adjusting the settings:
Содержание ATICS-2-63A-ISO
Страница 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Страница 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Страница 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Страница 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Страница 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...
Страница 100: ...100 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Technical data 10 2 T V test report according to VDE 0100 Part 710...
Страница 101: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 101 ATICS 2 63A ISO 10 3 T V certificate regarding functional safety...