Reference Manual
Capacitor Bank Protect. Relay KSR1
Rev. 10
2018-09
13
The alarm relay output can be configured as either latch able or non-latch able output.
The alarm relay goes back to inactive state as soon as the alarm value falls below the adjusted
threshold.
The alarm relay remains in active state even when the alarm value falls below the adjusted threshold.
To reset push the Button
for 3 sec. After a brownout, the relay falls back into the state before the
brownout.
The relay 3 is free to program to become active state with trip, alarm or both. Following settings are possible:
relay 3 is always switched off
relay 3 becomes active with alarm relay
relay 3 becomes active with trip relay
relay 3 becomes active with trip and alarm relay
relay 3 becomes active with trip or alarm relay
The relay 3 output can be configured as either latch able or non-latch able output.
The trip relay 3 goes back to inactive state as soon as the trip / alarm value fall below the adjusted
threshold.
The trip relay 3 remains in active state even when the trip / alarm value falls below the adjusted
threshold. To reset push the Button
for 3 sec. After a brownout, the relay falls back into the state
before the brownout.