Capacitor Bank Protect. Relay KSR1 

 

Rev. 10 

 

 

2018-09 

 

 

Important Information! 

If  this  sign  appears  besides  a  text  passage,  the  reader  is  strongly  advised  to  read  the  corresponding 

information,  because  it  is  very  important  for  the  device’s  usage!  It  can  indicate  safety  advices  or 

information  for  the  correct  handling  of  the  device.  If  the  information  is  disregarded,  the  device  may 

become inoperable or even damaged! 

1 Overview 

The KSR1 is designed to monitor medium and high voltage capacitor banks. The KSR1 can be set to monitor current or 

voltage, selectable in the menu. The device can monitor two threshold levels for Alarm / Trip. All thresholds / readings 

can be either a current or voltage value or a percentage setting of the maximum value. Once the Alarm or Trip level is 

reached,  the  appropriate  relay  will  operate  after  the  programmed  delay  time  has  elapsed.  Both  relays  can  be 

programmed to stay in the Alarm/Trip position until a reset is performed by the user. If it is required, alternatively they 

can be set to reset automatically, if the fault is cleared. A further relay can be used to signalize that an Alarm/Trip or 

both Alarm+Trip have been occurred. The KSR1 provides details of the last 5 Alarm and Trip operations.  

The KSR1 uses absolute values. For this reason, shown values are always positive independent of their actual direction 

(meas. value increases / decreases). 

Simplified diagram  

 

 

 

 

 

 

 

 

 

 

 

 

    Measured value   
–  Natural unbalance 
=  Value 

Comparator  

Value > limit 

Delay time 

Alarm / Trip 

Adjusted threshold 

Alarm / Trip 

Yes 

Yes 

No 

No 

Adjusted delay time 

for Alarm / Trip 

Monitoring blocked 

via DI1 & DI2 

Switch output relay 

Yes 

No 

Relay 1 TRIP 

Relay 3 progr. 

Relay 2 ALARM 

! 

Содержание KSR 1

Страница 1: ...Bank Protect Relay KSR1 Rev 10 2018 09 Beluk GmbH Taubenstrasse 1 D 86956 Schongau Germany Tel 49 0 8861 2332 0 Fax 49 0 8861 2332 22 E Mail blr beluk de http www beluk de Reference Manual Capacitor...

Страница 2: ...e 07 09 10 LE 02 Editorial changes Add technical data s 02 12 10 LE 03 Add changed menu points 02 03 11 LE 04 Add additional explanations 29 11 11 LE 05 Content update 26 11 12 LE 06 Change factory se...

Страница 3: ...ts 6 3 2 1 Measurement input 6 3 2 2 Blocking input 6 3 3 Outputs 7 3 3 1 Trip relay 7 3 3 2 Alarm relay 7 3 3 3 Relay 3 7 3 3 4 Status relay 7 3 4 User Interface 8 3 4 1 Keys 8 3 4 2 Display 8 3 4 3...

Страница 4: ...the maximum value Once the Alarm or Trip level is reached the appropriate relay will operate after the programmed delay time has elapsed Both relays can be programmed to stay in the Alarm Trip positi...

Страница 5: ...case of a failure For this reason it is recommended to monitor capacitor banks during operation in order to detect failures earlier Using the KSR1 there are two possible ways to set up a monitoring sy...

Страница 6: ...ction can cause malfunctions or can damage the device 3 2 Inputs 3 2 1 Measurement input The KSR1 has a voltage input as well as a current input Here the possible voltage range is 0 1 20 V and the mea...

Страница 7: ...ly closed and 21 24 are normally open no alarm condition In case the alarm trigger value voltage or current is exceeded for a longer period than the contacts 21 24 will close and 21 22 will open 3 3 3...

Страница 8: ...r right Confirmation of an input Decrease values Select menu items 3 4 2 Display The right side of the display shows the actually chosen main menu items The top line of the display shows the codes for...

Страница 9: ...blinks and its value can be altered in the same way as before When arriving the last digit press the key once more This position allows to set multipliers M Mega or k kilo To store the value press the...

Страница 10: ...d Displays the stored value of the natural unbalanced current Displays the adjusted threshold for trip Displays the adjusted time delay for trip Displays the adjusted threshold for alarm Displays the...

Страница 11: ...tarts blinking and shows the actual measured value To store the shown value push the button again To set a new value of the natural unbalance push the button again The stored value of the natural unba...

Страница 12: ...automatically by subsequent changes of the transformer ratio The input can be changed to percent in menu under Sets the delay time for alarm In case the alarm trigger value voltage or current is exce...

Страница 13: ...ram to become active state with trip alarm or both Following settings are possible relay 3 is always switched off relay 3 becomes active with alarm relay relay 3 becomes active with trip relay relay 3...

Страница 14: ...UM1 and UM2 Trip and alarm thresholds are given in V or in percentage of the nominal input range Values in percent All values are shown in percentage The thresholds for voltage or current are set in p...

Страница 15: ...blinks on the display An exceeding of the trip threshold is ignored Store alarm in Alarm buffer Alarms are stored with the trigger value in the Alarm buffer Alarms are not stored Drop off ratio hyster...

Страница 16: ...oring system is blocked when terminals DI1 DI2 are closed monitoring system is blocked when terminals DI1 DI2 are open Attention The digital input is activated or deactivated by opening or closing the...

Страница 17: ...together with the value which has triggered the event The alarm storage is a ring buffer which means an upcoming trip alarm deletes the oldest event if the buffer is full It is also possible to clear...

Страница 18: ...Alarm trip or both Relay 4 Status Max output rating AC 1250 VA max switching voltage 440 V AC Max output rating DC ohmic 30 V 5 A 60 V 1 A 110 V 0 5 A 220 V 0 3 A Digital input Blocking Alarm Trip vi...

Страница 19: ...ersion Fr Trip latchable trL tr4 Di state dl Alarm latchable ALL tr5 Relay 3 r3 AL1 Relay 3 latchable r3L AL2 AL3 200 Current voltage metering Cur AL4 Display absolute value or Per AL5 Transformer fac...

Страница 20: ...Reference Manual Capacitor Bank Protect Relay KSR1 Rev 10 2018 09 20 7 Dimensions...

Страница 21: ...0 s Trip latchable trL X Alarm latchable ALL X Relays 3 r3 X Relay 3 latchable r3L X Current voltage metering Cur X Display absolute value PEr X Transformer factor trF CT 1 4000 PT 1 350 1 Line freque...

Страница 22: ...Reference Manual Capacitor Bank Protect Relay KSR1 Rev 10 2018 09 22 Notes...

Отзывы: