Reference Manual
Capacitor Bank Protect. Relay KSR1
Rev. 10
2018-09
14
4.2.2
Expert menu
Password 511
To enter this menu select “Setup” and enter the expert password (511). Select submenus 100 – 400 by using
and
.
Enter the submenus by pushing
.
4.2.2.1
Start menu
Contains the same settings as start menu above.
4.2.2.2
Measurement menu
Current measuring
The KSR1 measures the current at input K and L. Trip and alarm thresholds are given in A or in
percentage of the nominal input range.
The KSR1 is measuring the voltage at input UM1 and UM2. Trip and alarm thresholds are given in V or
in percentage of the nominal input range.
Values in percent
All values are shown in percentage. The thresholds for voltage or current are set in percentage of the
nominal value of the input.
All values are shown as absolute value. The thresholds for voltage or current are set as absolute value.
Attention: A previous adjusted Transformerratio become set to 1 when altering this item.
Transformer factor
Voltage: adjustable VT ratio from 1-350.
Current: adjustable CT ratio from 1-4000.
Frequency
Here, it is possible to adjust the mains frequency. Possible settings are 50 Hz and 60 Hz. The frequency setting should
be correct otherwise the measurement does not work proper.
!