Reference Manual
Capacitor Bank Protect. Relay KSR1
Rev. 10
2018-09
16
The KSR1 uses absolute values. For this reason, shown values are always positive independent of their actual
direction (meas. value increases / decreases).
Digital input active
the monitoring system can be blocked via the digital input.
the monitoring system cannot be blocked via the digital input.
Digital input open or closed
monitoring system is blocked when terminals DI1 & DI2 are closed.
monitoring system is blocked when terminals DI1 & DI2 are open.
Attention: The digital input is activated or deactivated by opening or closing the contact DI1 and DI2. Connecting
a voltage signal can destroy the KSR1.
4.2.2.4
Reset menu
reset trip
reset alarm
reset stored alarms and trips
reset natural unbalance
reset the device to factory settings.
change password “setup”. Possible adjustment 000-999. Master password 242.
change password “expert”. Possible adjustment 000-999. Master password 511.
To switch off the password protection, set
to 000.
!
!