Reference Manual
Capacitor Bank Protect. Relay KSR1
Rev. 10
2018-09
21
8 Settings
Parameter
Range
Factory settings
Customer settings
Natural unbalanced I “NU"
Trip value "trd"
20 mA – 5 A / 200 mV – 20 V
3
1 V / 1 A
Trip time“trt”
0,1-100 s
0,5 s
Alarm value“Ald”
20 mA – 5 A / 200 mV-20 V
3
5 V / 5 A
Alarm time“Alt”
0,1-100 s
1,0 s
Trip latchable“trL”
X
Alarm latchable“ALL”
X
Relays 3 „r3“
X
Relay 3 latchable “r3L”
X
Current / voltage metering „Cur“
X
Display absolute value“PEr”
X
Transformer factor “trF”
CT 1-4000 / PT 1-350
1
Line frequency „Frq“
50 / 60
50
Trip active“tr”
X
Store trip in buffer “trs”
X
Alarm active “AL”
X
Store alarm in buffer “ALS”
X
Drop off ratio “dor”
50% - 100%
90%
Activate DI “dI”
X
DI open or closed “dIL”
X
Password „Setup“
242
Password „Expert“
511
3
When using a VT / CT the set thresholds are multiplied by the adjusted transformer ratio.