5.1 Design guidelines
25
5 Startup
OZD Profi G12D... ATEX 1 V. 03 07/2014
5 Startup
5.1.2 Assembly in zone 2
OZD Profi G12DU ATEX 1 devices shall be installed into
an enclosure that complies with one of
the following types of protection as a minimum according
to the respective field of application :
"lncreased Safety", "Flameproof Enclosure" or "Protec-
tion by Enclosure".
OZD Profi G12DK/DE ATEX 1 devices may be installed in
gas-ex in zone 2 or for dust-ex in zone 22.
IP5* must be complied with for non-conductive dust and
IP6* for conductive dust.
The housing cover may be opened for servicing during
ongoing operation.
All terminals are covered.
The cover may be removed in zone 2 and also in the safe
area for servicing. The terminals are then accessible.
Non-used inlet openings are to be sealed securely with
certified sealing plugs in order to comply with the IP pro-
tection class. Likewise, seal inserts appropriate for the
respective cable diameter must be used.
Excessive force on the glands may endanger the
protection class.
5.1.3 Assembly in safe area
The device types can be installed outside the ex-area.
The housing cover may be opened for servicing during
ongoing operation.
Terminals in increased safety are covered.
The cover may be removed any time during assembly in
safe area.
5.1.1 Assembly in zone 1
OZD Profi G12DU ATEX 1 devices shall be installed into
an enclosure that complies with one of
the following types of protection as a minimum accord-
ing to the respective field of application :
"lncreased Safety", "Flameproof Enclosure" or "Protec-
tion by Enclosure".
OZD Profi G12DK/DE ATEX 1 devices may be installed in
gas-ex in zone 1 or for dust-ex in zone 21.
The housing cover may be opened in zone 1 for servicing
during ongoing operation.
The housing cover for dust-ex in zone 21 is opened only
in currentless state or with hot work permit.
Terminals in increased safety are covered.
The cover may be removed only if there is no explosion
hazard (hot work permit) or circuits are switched to zero
potential beforehand.
Non-used inlet openings are to be sealed securely with
certified sealing plugs in order to comply with the IP pro-
tection class. Likewise, seal inserts appropriate for the
respective cable diameter must be used.
Excessive force on the glands may endanger the protec-
tion class.
5.1 Design guidelines