PF1352 USER MANUAL REV A 12/21/15
SECTION TWO
INSTALLATION AND WIRING
2.1 INSTALLATION
This device is designed primarily for desktop or bench top operation. This model may
also be mounted in an EIA standard equipment rack using the RM adaptor kit available
from Behlman. If the unit is to be rack mounted, it must be placed so as not to block the
cooling vents on the sides, top, and rear panels. Rear support must also be provided.
This may be in the form of internal support “rails” or chassis slides. Many equipment
rack manufacturers can supply generic support brackets or shelves to be used with their
racks. Racks that are completely sealed will require ventilation to remove heat
generated by the AC power supply’s exhaust.
The installation site must protect the power supply from moisture and any conductive
particulate matter.
IN NO CASE
should this unit be operated in the presence of dripping
or misting fluids. For continuous full power output, the ambient operating temperature
should not exceed 40 degrees Celsius.
WARNING !
INSTALLATION AND OPERATION
MAY EXPOSE PERSONNEL TO HAZARDOUS
VOLTAGE AND CURRENT LEVELS
2.2
INPUT POWER CONNECTION
This unit operates from any AC voltage from 95 -270V with a frequency between 47 and
63 Hertz. A detachable line cord is provided that mates with the IEC-19 type receptacle
(J1) on the rear panel. The other end of the supplied line cord is left un-terminated so
that the end user can affix the proper plug to mate with power receptacles available at
the installation site. Conformance to IEC safety standards limits the input to 250VAC.
WARNING
THIS DEVICE IS SUPPLIED WITH A 3 WIRE LINE CONNECTION THAT INCLUDES A PROTECTIVE
EARTH CONDUCTOR (YEL/GREEN WIRE). THIS CONNECTION IS CRITICAL TO OPERATOR
SAFETY AND MUST BE TIED TO THE INSTALLATION SITE PROTECTIVE EARTH. DUE TO
COMPONENTS USED FOR EMI REDUCTION, THIS DEVICE MAY PRODUCE LEAKAGE CURRENTS
THAT ARE HAZARDOUS. THE EARTH CONNECTION PROVIDES A RETURN PATH FOR THESE
CURRENTS.