Interlock Thermocouple
(Shown here fitted into the
Flue Transition using a
Gland nut)
Thermocouple cable
(Wired into Gas
control box)
Alternate fitting position
if space is not available
above oven
(Side of Flue Transition)
Interlock System - Australian markets ONLY.
For all Gas fired Oven installations within Australia, there is a requirement by the
Australian Gas Association
(AGA)
for the Gas system of your Beech Oven to comply
with the Gas Installation Standard AS5601.
To meet this requirement, all Gas fired Beech Ovens are required to be fitted with a
“Power flue” system of exhaust extraction. This is to safeguard against spillage of
combustion product gases into the kitchen area. In line with this requirement, it is
required that the Gas system of the oven is interlocked with the performance of the
Flue. If the flue performance deteriorates
(so that spillage may occur)
the Gas system
should shut off and “lock-out” in such a manner that to re-start the Gas system, the
operator must manually reset the system.
(This will give warning to the operator that
there may be a problem with the
“Power Flue.”)
To reset the system, turn the Main Control switch on the front of the Gas control cabinet
to
OFF,
then
ON
again.