FC310x as master
FC3101 and FC3102
61
Version: 3.0
PROFIBUS Error
: It is possible to specify the reaction to a PROFIBUS error here (reaction in the output data
in the coupler)
Measure Coupler-Cycle
: It is possible here to measure the cycle time for the coupler (DP + K-Bus); the K-
bus update time is sometimes rather imprecise for synchronized processes.
3.9.4
ProcessData tab
Fig. 37: ProcessData tab
Under Siemens AG or Profidrive MC, the boxes Profidrive MC and Profidrive MC (twice) may be selected. By
default the box is allocated the settings for a Simodrive 611U with standard telegram 3. For other PROFIBUS
MC slaves, the ID number on the
tab of the slave has to be changed accordingly. The
required telegram type can be set on the
ProcessData
tab and must usually correspond with parameter 922
of the PROFIBUS MC slave, which can be set via a manufacturer-specific configuration tool (SimoCon U for
Simodrive 611U).
This tab also contains a "PKW interface" checkbox, which activates the PKW interface. In online mode, this
can be used to display the box parameters on the Online tab (at present this only works with the Simodrive
611U, since a parameter file is required, which is generated by the SimoCon U). In any case it is possible to
read and write the parameters via the PKW interface per ADS (see chapter
).