FC310x as master
FC3101 and FC3102
38
Version: 3.0
Error code
Meaning
0x2131
Write general: wrong IndexGroup
0x2132
Write general: wrong IndexGroup
0x2137
PKW-Read: WORD received, but read data length does not equal 2
0x2138
PKW-Read: DWORD received, but read data length does not equal 4
0x2139
PKW-Read: unknown AK received (1,2 or 7 expected)
0x213A
PKW-Read-Array: WORD received, but read data length does not equal 2
0x213B
PKW-Read-Array: DWORD received, but read data length does not equal 4
0x213C
PKW-Read-Array: unknown AK received (4,5 or 7 expected)
0x213D
PKW-Write-Array: unknown AK received (2 or 7 expected)
0x213E
PKW-Write: unknown AK received (1 or 7 expected)
0x213F
PKW-Write: unknown AK received (2 or 7 expected)
0x2140
PKW-Write-Array: unknown AK received (1 or 7 expected)
0x2142
SetSlaveAddress: wrong parameter during setting of address in slave mode
0x2144
Incorrect IndexGroup in ReadWrite
0x2147
DPV1-C2-Initiate: MSAC_C2 is not activated
0x2148
Incorrect IndexGroup in Read
0x2149
Incorrect IndexGroup in Write
0x214E
DPV1-C2-Read: MSAC_C2 is not activated
0x214F
DPV1-C2-Write: MSAC_C2 is not activated
0x2150
DPV1-C2-DataTransport: MSAC_C2 is not activated
0x2151
DPV1-C2-Read: FDL fault (no response etc.)
0x2152
DPV1-C2-Read: connection aborted
0x2153
DPV1-C2-Read: DPV1 fault (4 bytes error code in the diagnostic data of the slave)
0x2154
PKW-ReadNoOfElements: length must equal 1
0x2155
PKW-ReadNoOfElements: PKW is not activated
0x2156
PKW-ReadNoOfElements: axis number is too great
0x2157
PKW-ReadNoOfElements: slave not in data exchange
0x2158
PKW-ReadNoOfElements: unknown AK received (6 or 7 expected)
0x215A
DPV1-C2-Write: FDL fault (no response etc.)
0x215B
DPV1-C2-Write: connection aborted
0x215C
DPV1-C2-Write: DPV1 fault (4 bytes error code in the diagnostic data of the slave)
0x215D
DPV1-C2-DataTransport: FDL fault (no response etc.)
0x215E
DPV1-C2-DataTransport: connection aborted
0x215F
DPV1-C2-DataTransport: DPV1 fault (4 bytes error code in the diagnostic data of the
slave)
0x2163
DPV1-C2-DataTransport: Incorrect IndexOffset
0x2600-0x26FF AK 7 (error) during PKW processing, error code in low byte
0x2700-0x27FF Fault during DPV1 processing, 4 bytes error code in the slave diagnostic data, byte 3 of the
error code (error class, error code) is in Low byte
3.7
Master redundancy
It is possible to start the DP master in redundancy mode in order to assemble a redundant control system. In
this case, the DP master only listens to the bus, but is not active on it.
To assemble a redundant control system, two masters are on the PROFIBUS (both have identical
configurations): the primary master, which performs communication under normal circumstances, and the
redundancy master, which only listens to the bus without transmitting. The only difference in the PROFIBUS
configuration between primary and redundant master should be in the settings
Redundancy Mode
and