Commissioning
EL47xx
97
Version: 2.7
State Machine
Init
This button attempts to set the EtherCAT device to the
Init
state.
Pre-Op
This button attempts to set the EtherCAT device to the
pre-operational
state.
Op
This button attempts to set the EtherCAT device to the
operational
state.
Bootstrap
This button attempts to set the EtherCAT device to the
Bootstrap
state.
Safe-Op
This button attempts to set the EtherCAT device to the
safe-operational
state.
Clear Error
This button attempts to delete the fault display. If an EtherCAT slave fails during
change of state it sets an error flag.
Example: An EtherCAT slave is in PREOP state (pre-operational). The master now
requests the SAFEOP state (safe-operational). If the slave fails during change of state
it sets the error flag. The current state is now displayed as ERR PREOP. When the
Clear Error
button is pressed the error flag is cleared, and the current state is
displayed as PREOP again.
Current State
Indicates the current state of the EtherCAT device.
Requested State
Indicates the state requested for the EtherCAT device.
DLL Status
Indicates the DLL status (data link layer status) of the individual ports of the EtherCAT slave. The DLL status
can have four different states:
Status
Description
No Carrier / Open
No carrier signal is available at the port, but the port is open.
No Carrier / Closed
No carrier signal is available at the port, and the port is closed.
Carrier / Open
A carrier signal is available at the port, and the port is open.
Carrier / Closed
A carrier signal is available at the port, but the port is closed.
File Access over EtherCAT
Download
With this button a file can be written to the EtherCAT device.
Upload
With this button a file can be read from the EtherCAT device.
"DC" tab (Distributed Clocks)
Fig. 123: "DC" tab (Distributed Clocks)
Operation Mode
Options (optional):
• FreeRun
• SM-Synchron
• DC-Synchron (Input based)
• DC-Synchron
Advanced Settings…
Advanced settings for readjustment of the real time determinant TwinCAT-
clock
Detailed information to Distributed Clocks are specified on
:
Содержание EL47 Series
Страница 1: ...Documentation EL47xx Analog output terminal with oversampling 2 7 2020 02 27 Version Date...
Страница 2: ......
Страница 33: ...Mounting and wiring EL47xx 33 Version 2 7 Fig 23 Other installation positions...
Страница 70: ...Commissioning EL47xx 70 Version 2 7 Fig 73 Incorrect driver settings for the Ethernet port...
Страница 81: ...Commissioning EL47xx 81 Version 2 7 Fig 92 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...
Страница 144: ...Commissioning EL47xx 144 Version 2 7 Fig 178 Selecting the EL4732 terminal Fig 179 Terminal in the TwinCAT tree...
Страница 149: ...Commissioning EL47xx 149 Version 2 7 Fig 184 Process data tab SM1 EL47xx...
Страница 156: ...Commissioning EL47xx 156 Version 2 7 Fig 195 Process Data tab adaptation of process data in SM0...