Commissioning
EL47xx
112
Version: 2.7
The Task has to be inserted as “TwinCAT Task With Image” and also creates an “Inputs” and “Outputs”
folder therefore. The properties of the new (or as the case may be already existing) task must have activated
the attribute “Create symbols” to make them selectable by the “Target Browser” of the Scope later on. The
task cycle time has to be changed if so. Then, with10 x Oversampling 1 ms at 100 µs base time, resulting 10
ticks will be set by the usage of the EL3751 for example:
Fig. 137: Task property "Create symbols" must be activated
There’s a default value given for the Port number (301) that should be changed, if necessary. This number
has to make acquainted for the Scope, if applicable, later on. By a right click on “Inputs” that oversampling
based variable can now be appended with the fitting datatype of an array. „ARRAY [0..9] OF DINT“ referred
to as „Var 1“ in this case:
Fig. 138: Insertion of variable "Var 1" fitting to the oversampling (-factor)
Step 3: Linking an array variable with an oversampling PDO
By right click on “MAIN.aUI_Samples” (according to the last preceding paragraph Step 2a) or rather
“Var 1” (according to the last preceding paragraph Step 2b) within the Solution Explorer a window opens to
select the process data:
Содержание EL47 Series
Страница 1: ...Documentation EL47xx Analog output terminal with oversampling 2 7 2020 02 27 Version Date...
Страница 2: ......
Страница 33: ...Mounting and wiring EL47xx 33 Version 2 7 Fig 23 Other installation positions...
Страница 70: ...Commissioning EL47xx 70 Version 2 7 Fig 73 Incorrect driver settings for the Ethernet port...
Страница 81: ...Commissioning EL47xx 81 Version 2 7 Fig 92 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...
Страница 144: ...Commissioning EL47xx 144 Version 2 7 Fig 178 Selecting the EL4732 terminal Fig 179 Terminal in the TwinCAT tree...
Страница 149: ...Commissioning EL47xx 149 Version 2 7 Fig 184 Process data tab SM1 EL47xx...
Страница 156: ...Commissioning EL47xx 156 Version 2 7 Fig 195 Process Data tab adaptation of process data in SM0...