Commissioning
EL47xx
115
Version: 2.7
Now the program start has to be done with
formally although there’s no program still yet. Using “Start
Recording“
the process data value of the oversampling PDO “L1 Voltage Samples “ via the linked PLC
array variable can be recorded time dependent now.
As an example a sine wave input measurement value (204.5 Hz) will be illustrated below:
Fig. 143: Example of recording a sine signal with 10 x oversampling at 1 ms measurement cycle time
The X-axis view was fitted properly by using “Panning X”
after the recording was stopped
.
Following the “Chart” property “Use X-Axis SubGrid” was set to true with 10 divisions as well as the
“ChannelNodeProperties” attribute “Marks” was set to “On” with the colors “Line Color” blue and “Mark Color”
red. Therefore the latter indicates that 10 oversampling measurement points by the red marks.
Proceeding with / via ADS alternatively
In former TwinCAT 3 versions (or a lower revision as specified in the
above) the oversampling
PDO of the respective oversampling able terminal/box can be made visible for the ScopeView by activation
of the ADS server.
Содержание EL47 Series
Страница 1: ...Documentation EL47xx Analog output terminal with oversampling 2 7 2020 02 27 Version Date...
Страница 2: ......
Страница 33: ...Mounting and wiring EL47xx 33 Version 2 7 Fig 23 Other installation positions...
Страница 70: ...Commissioning EL47xx 70 Version 2 7 Fig 73 Incorrect driver settings for the Ethernet port...
Страница 81: ...Commissioning EL47xx 81 Version 2 7 Fig 92 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...
Страница 144: ...Commissioning EL47xx 144 Version 2 7 Fig 178 Selecting the EL4732 terminal Fig 179 Terminal in the TwinCAT tree...
Страница 149: ...Commissioning EL47xx 149 Version 2 7 Fig 184 Process data tab SM1 EL47xx...
Страница 156: ...Commissioning EL47xx 156 Version 2 7 Fig 195 Process Data tab adaptation of process data in SM0...