Commissioning
EL47xx
153
Version: 2.7
"StartTimeNextOutput" activation
The assigned process record "StartTimeNextOutput" for transfer to the EtherCAT bus can be enabled by
entering 0x1A82 in the field below, after selecting Sync Manager 2 (Fig.
Process data tab, activation of index
0x1A82, entry „StartTimeNextOutput
“, top left).
Fig. 190: Process data tab, activation of index 0x1A82, entry “StartTimeNextOutput”
The StartTimeNextOutput process data is 32 bits wide. During each process data cycle the time is specified
at which the
next
SYNC1 pulse and therefore the next block of sample values begins. This time is based on
the terminal-specific local distributed clock time. The EL47xx only maps the lower 32 bits of the generally 64-
bit distributed clock time.
In this way all samples can be synchronized with other time data within the EtherCAT system based on the
known oversampling factor.
Sample:
With an oversampling factor of n = 20 and a StartTimeNextOutput = 0x12345678, the next sample block of
20 samples therefore starts at the distributed clocks time of 0x123456678
hex
or 305,419,896 ns.
Fig. 191: TwinCAT tree, entry "StartTimeNextOutput"
Содержание EL47 Series
Страница 1: ...Documentation EL47xx Analog output terminal with oversampling 2 7 2020 02 27 Version Date...
Страница 2: ......
Страница 33: ...Mounting and wiring EL47xx 33 Version 2 7 Fig 23 Other installation positions...
Страница 70: ...Commissioning EL47xx 70 Version 2 7 Fig 73 Incorrect driver settings for the Ethernet port...
Страница 81: ...Commissioning EL47xx 81 Version 2 7 Fig 92 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...
Страница 144: ...Commissioning EL47xx 144 Version 2 7 Fig 178 Selecting the EL4732 terminal Fig 179 Terminal in the TwinCAT tree...
Страница 149: ...Commissioning EL47xx 149 Version 2 7 Fig 184 Process data tab SM1 EL47xx...
Страница 156: ...Commissioning EL47xx 156 Version 2 7 Fig 195 Process Data tab adaptation of process data in SM0...