Mounting and wiring
EL3632
41
Version: 2.8
4.9
LEDs and connection
Fig. 32: LEDs
LEDs
LED
Color
Meaning
RUN
green
This LED indicates the terminal's operating state:
off
State of the
:
INIT
= initialization of the terminal
flashing
State of the EtherCAT State Machine:
PREOP
= function for mailbox communication and dif-
ferent standard-settings set
single flash
State of the EtherCAT State Machine:
SAFEOP
channels and the distributed clocks.
Outputs remain in safe state
on
State of the EtherCAT State Machine:
OP
= normal operating state; mailbox and process data
communication is possible
Error 1/2
red
Open circuit error
Connection EL3632
Fig. 33: Connection
Note: Terminal point 2 and 6 (- Input of the channels) are internally linked. Thus, a multichannel IEPE sensor
can be connected, that supports one GND returning wire only. If a three channel sensor (3 axis, triaxis) will
be connected via two terminals, each GND and respectively each -Input have to bridged.