Commissioning
EJ6002
43
Version: 1.5
6.2.3
Input data
Index 60n0 COM Inputs Ch. 1 (n = 0), Ch. 2 (n = 1)
Index
(hex)
Name
Meaning
Data type
Flags Default
60n0:0
COM Inputs Ch. (n+1)
Length of this object
UINT8
RO
0x26
(38
dec
)
60n0:01 Transmit accepted
The module acknowledges the receipt of data with a change of
state of this bit.
Only then are new data transferred from the controller to the
module.
BOOLEAN
RO
0x00
(0
dec
)
60n0:02 Receive request
By changing the state of this bit, the module notifies the con-
troller that the number of bytes indicated in index 0x60n0:09 "In-
put length" are located in the DataIn bytes.
The controller must acknowledge receipt of the data with a
change of state of the "Receive accepted" bit (index 0x70n0:02).
Only then is new data transferred from the module to the con-
troller.
BOOLEAN
RO
0x00
(0
dec
)
60n0:03 Init Accepted
FALSE:
The module is once again ready for serial data exchange.
TRUE:
The initialization was executed by the module.
BOOLEAN
RO
0x00
(0
dec
)
60n0:04 Buffer full
The receive FIFO is full.
Note
All incoming data will be lost from this point on!
BOOLEAN
RO
0x00
(0
dec
)
60n0:05 Parity error
A parity error has occurred.
BOOLEAN
RO
0x00
(0
dec
)
60n0:06 Framing error
A framing error has occurred.
BOOLEAN
RO
0x00
(0
dec
)
60n0:07 Overrun error
An overrun error has occurred.
BOOLEAN
RO
0x00
(0
dec
)
60n0:09 Input length
Number of input bytes ready for transfer from the module to the
controller.
UINT8
RO
0x00
(0
dec
)
60n0:11 Data In 0
Input byte 0
UINT8
RO
0x00
(0
dec
)
…
…
…
…
…
…
60n0:26 Data In 21
Input byte 21
UINT8
RO
0x00
(0
dec
)
Index 60n1 Com Ext. Inputs Ch. 1 (n = 0), Ch.2 (n = 1)
Index
(hex)
Name
Meaning
Data type
Flags Default
60n1:0
Com Ext. Inputs Ch.(n+1)
Length of this object
UINT8
RO
0x02
(2
dec
)
60n1:01 Rx
In operation mode
“RS232, manual operation” (CoE
= 17
dec
) or
“RS232, manual flow control” (CoE
= 18
dec
) the
level of Rx input is displayed here.
BOOLEAN
RO
0x00
(0
dec
)
60n1:02 CTS
In operation mode
“RS232, manual operation” (CoE
= 17
dec
) or
“RS232, manual flow control” (CoE
= 18
dec
) the
level of CTS input is displayed here.
BOOLEAN
RO
0x00
(0
dec
)