Commissioning
EJ6002
40
Version: 1.5
6.2.1
Restore object
Index 1011 Restore default parameters
Index
(hex)
Name
Meaning
Data type
Flags Default
1011:0
Restore default parame-
ters
Restore default parameters
UINT8
RO
0x01 (1
dec
)
1011:01
SubIndex 001
If this object is set to
“0x64616F6C”
in the set value dia-
log, all backup objects are reset to their delivery state.
UINT32
RW
0x00000000 (0
dec
)
6.2.2
Configuration data
Index 80n0 COM Settings Ch.1 (n = 0), Ch.2 (n = 1)
Index
(hex)
Name
Meaning
Data type
Flags Default
80n0:0
COM Settings Ch.(n+1) Max. Subindex (hex)
UINT8
RO
0x1D (29
dec
)
80n0:01
Enable RTS/CTS
FALSE:
RTS/CTS not enabled
TRUE:
enabled
BOOLEAN
RW
0x01 (1
dec
)
80n0:02
Enable XON/XOFF sup-
ported tx data
FALSE:
XON/XOFF is not supported for send data
TRUE:
XON/XOFF is supported for send data
BOOLEAN
RW
0x00 (0
dec
)
80n0:03
Enable XON/XOFF sup-
ported rx data
FALSE:
XON/XOFF is not supported for input data
TRUE:
XON/XOFF is supported for input data
BOOLEAN
RW
0x00 (0
dec
)
80n0:04
Enable send FIFO data
continuous
FALSE:
No continuous sending of data from the FIFO
TRUE:
Continuous sending of data from the FIFO enabled:
• The send buffer is filled (up to 128 bytes) by the
controller.
• The filled buffer content is sent with a rising edge of
the bit "Send continuous" (0x70n0:04).
• The module acknowledges the data transfer to the
controller by setting the bit "Init accepted"
(0x60n0:03). "Init accepted" is reset with "Send
continuous".
BOOLEAN
RW
0x00 (0
dec
)
80n0:05
Enable transfer rate op-
timization
FALSE:
Transfer rate optimization switched off
TRUE:
Transfer rate optimization switched on:
The content of the input buffer is automatically trans-
ferred into the process image if
• no further byte was received for approx. 16 bit times
(the time it would have taken to receive 2 bytes)
after receiving data.
• the process image is filled
BOOLEAN
RW
0x01 (1
dec
)
80n0:06
Enable half duplex
FALSE:
Full-duplex mode
TRUE:
Half-duplex mode
BOOLEAN
RW
0x00 (0
dec
)