Parameterization and commissioning
CX8050, CX8051 - Embedded-PCs for
CANopen and CAN
33
Version: 1.4
6
Parameterization and commissioning
6.1
DIP switch
CAUTION
DIP switches as ignition source in potentially explosive atmospheres
Gases or dusts can be ignited by a spark discharge when DIP switches are used.
Switch off the power supply and wait until the 1-second UPS has discharged. Ensure that
there is no explosive atmosphere before you use DIP switches.
CX8050 DIP switch
The address selection switch of the CX8050 has no purpose, although it can be read by the PLC (see
programming).
CX8051 DIP switch
2x 10-pole address switch S101/S102
The address selection switch can be used for CAN address, although it can also be read by the PLC (see
programming).
S101 for the address x 1, S102 for the address x10, example S101=2, S102=3 CAN node address 32
So that the address is also used via the address selector, this must be activated in the System Manager.