Programming
CX8050, CX8051 - Embedded-PCs for
CANopen and CAN
57
Version: 1.4
NodeState value
Description
0
No error
1
Node deactivated
2
Node not found
4
SDO syntax error at Start Up
5
SDO data mismatch at Start Up
8
Node start up in progress
11
Bus-OFF
12
Pre-Operational
13
Servere bus fault
14
Guarding: toggle error
20
TxPDO too short
22
Expected TxPDO is missing
23
Node is Operational but not all TxPDOs were
received
ADS Port 200
Reading of emergency telegrams with AdsRead
Input parameters
Description
NETID
NetId of the CAN interface
Port number
200
IDXGRP
16#xxxxF180 (xxxx) Node-Id, the Diag flag is only
reset when at least 106 bytes are read
16#xxxxF181 (xxxx) Node-Id, the Diag flag is reset
immediately
IDXOFFS
Byte Offset