3
Installation
3.1
Important notes
l
Protect the servo amplifier from impermissible stresses. In particular, do not let any
components become bent or any insulation distances altered during transport and
handling. Avoid contact with electronic components and contacts.
l
Check the combination of servo amplifier and motor. Compare the rated voltage and
current of the units. Carry out the wiring according to the instructions on page 27.
l
Make sure that the maximum permissible rated voltage at the terminals for L1, L2, L3
and +R
Bext
, –DC is not exceeded by more than 10%, even in the most unfavourable
conditions (see EN 60204-1 Section 4.3.1). An excessive voltage on these terminals
can lead to destruction of the regen circuit and the servo amplifier.
Use the AX251x only on an earthed 3-phase supply system. Use the amplifier only to
drive a synchronous servomotor.
l
The fusing of the AC supply input and the 24V supply is installed by the user
(
ð
l
Take care that the servo amplifier and motor are properly earthed. Do
not
use pain-
ted (non-conductive) mounting plates.
l
Route power and control cables separately. We recommend a separation of at least
20 cm. This improves the interference immunity required by EMC regulations. If a
motor power cable is used which includes cores for brake control,
the brake control
cores must be separately shielded
. Earth the shielding at both ends (
ð
l
Install all heavy-current cables with an adequate cross-section, as per EN 60204-1
(
ð
p.17) and use the requested cable material (
ð
p. 33) to reach max. cable length.
l
Wire the BTB/RTO contact in series into the safety circuit of the installation.
Only in this way is the monitoring of the servo amplifier assured.
l
Install all shielding with large area (low impedance) connections, with metallised con-
nector housings or shield connection clamps where possible.
Notes on connection techniques can be found on page 32.
l
Ensure that there is an adequate flow of cool, filtered air into the bottom of the control
cabinet or use heat exchanger. Note the conditions on page 17 .
l
It is permissible to alter the servo amplifier settings by using the operator software.
Any other alterations will invalidate the warranty.
Caution
Never disconnect the electrical connections to the servo amplifier while it is live.
Residual charges in the capacitors can have dangerous levels up to 300 seconds
after switching off the mains supply voltage. Measure the voltage in the DC Bus
link (+R
Bext
/-DC) and wait until the voltage has fallen below 40V.
Control and power connections can still be live, even when the motor is not
rotating.
AX2500 Installation Manual
23
Beckhoff
02/06
Installation
Содержание AX2500 Series
Страница 22: ...This page has been deliberately left blank 22 AX2500 Installation Manual Technical description 02 06 Beckhoff...
Страница 26: ...3 3 1 Dimensions 26 AX2500 Installation Manual Installation 02 06 Beckhoff AX250x and AX251x AX252x...
Страница 31: ...3 4 4 Connector assignments AX2500 Installation Manual 31 Beckhoff 02 06 Installation...
Страница 36: ...This page has been deliberately left blank 36 AX2500 Installation Manual Installation 02 06 Beckhoff...
Страница 60: ...This page has been deliberately left blank 60 AX2500 Installation Manual Interfaces 02 06 Beckhoff...
Страница 65: ...5 3 2 3 Status display on the master AX2500 Installation Manual 65 Beckhoff 02 06 Setup...
Страница 68: ...This page has been deliberately left blank 68 AX2500 Installation Manual Setup 02 06 Beckhoff...
Страница 81: ...This page has been deliberately left blank AX2500 Installation Manual 81 Beckhoff 02 06 Appendix...