8.17.6
Functional test
The functioning of the restart lock must be tested during setup, after every
alteration in the wiring of the system, or after exchanging one or more components
of the system.
1.
Stop all drives, with setpoint 0V, disable drives, mechanically block any suspended loads
2.
Activate the restart lock -AS-.
3.
Open protective screens (but do not enter hazardous area)
4.
Pull off the X10 connector from an amplifier:
the mains contactor must drop out
5.
Reconnect X10. Switch on mains contactor again.
6.
Repeat steps 4 and 5 for each individual servo amplifier.
8.17.7
Connection diagram (principle)
Application examples for category 1 see chapters 8.17.8.